Minimum Clearances To Combustible Material - Town & Country Fireplaces TC36 Instruction Manual

Table of Contents

Advertisement

Minimum Clearances to Combustible Material

COMBUSTIBLE FRAMING AND
FINISH WALL ABOVE STANDOFFS
MAY USE COMBUSTIBLE
FACING MATERIAL IN THIS
AREA
NON-COMBUSTIBLE
FINISH MATERIAL
SEE FIG #14 & 15
D
A
B
TOP OF LINTEL BAR
FIREPLACE FRONT
Figure 3:
TC 36 Mantle clearances.
CEILING
24"
32 1/2"
UNIT MAY BE RECESSED UP TO 4 1/2" WITH
NON-COMBUSTIBLE MASONRY TYPE
MATERIAL
Figure 4:
TC 36D Mantle.
5056.427D
STEEL FRAMING
STANDOFFS
E
F
C
MANTEL
ADJACENT WALL
OR MANTEL
SUPPORT
4"
NON-COMBUSTIBLE ZONE.
DO NOT INSTALL ANY COMBUSTIBLE
MATERIAL, ELECTRICAL WIRING OR GAS
PLUMBING IN THIS AREA.
Minimum Clearances:
Side standoffs .................................................... 0 in. (0 mm)
Back standoffs ................................................... 0 in. (0 mm)
Top standoffs ...................................................... 0 in. (0 mm)
Bottom of appliance ........................................... 0 in. (0 mm)
Adjacent side wall .............................................. 4 in. (102 mm)
Ceiling to appliance .......................................... 24 in. (610 mm)
*Mantel to appliance ................................... (Figure 3)
**Maximum Mantel extension ..................... (Figure 3)
Mantel support ................................................... 4 in. (102 mm)
Vertical vent pipe ........................................1 3/4" in. (45 mm)
Horizontal Vent pipe (Top, sides and bottom) 1 3/4" in. (45 mm)
6
MANTEL CLEARANCE
CHART
* MANTEL CLEARANCE
A
9"
B
6"
C
3"
** MANTEL DEPTH
D
12"
E
6 3/4"
F
1 1/2"
TC36_D & TC36_DAR_101215-52