Func.
Name
Code

Maximum-limit level of window
comparator (O)

Minimum-limit level of window
comparator (O)

Hysteresis width of window
comparator (O)

Maximum-limit level of window
comparator (OI)

Minimum-limit level of window
comparator (OI)

Hysteresis width of window
comparator (OI)

Operation level at O
disconnection

Operation level at OI
disconnection

Ambient temperature setting

Watt-hour clearance

Watt-hour display gain

Start frequency

Carrier frequency

Initialization mode (parameters
or trip history)

Country for initialization

Frequency scaling conversion
factor

STOP key enable
"b" Function
Description
Set range, {Min.-limit level () +
hysteresis width ()x2} to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level
() - hysteresis width
()x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level
() - Min.-limit level ()}/2 %
(Maximum of 10%)
Set range, {Min.-limit level ( +
hysteresis width ()x2} to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level
() - hysteresis width
()x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level
() - Min.-limit level ()}/2 %
(Maximum of 10%)
Set range, 0 to 100%, or "no"
(ignore)
Set range, 0 to 100%, or "no"
(ignore)
Set range is,
-10 to 50 C
Two option codes:
OFF
ON (press STR then clear)
Set range is,
1. to 1000.
Sets the starting frequency for the
inverter output, range is 0.10 to 9.99
Hz
Sets the PWM carrier (internal
switching frequency), range is 2.0 to
15.0 kHz
Select initialized data, five option
codes:
Initialization disabled
Clears Trip history
Initializes all Parameters
Clears Trip history and
initializes all parameters
Clears Trip history and
initializes all parameters and
EzSQ program
Mode 1
Specify a constant to scale the
displayed frequency for 
monitor, range is 0.01 to 99.99
Select whether the STOP key on the
keypad is enabled, three option
codes:
Enabled
Disabled always
 Disabled for stop
65
Run
Defaults
Mode
Initial data
Units
Edit
100.
%
0.
%
0.
%
100.
%
0.
%
0.
%
no
-
no
-
C
40
00
-
1.
0.50
Hz
10.0
kHz
00
01
1.00
00