Func.
Name
Code
Free V/F setting, freq.1
Free V/F setting, voltage.1
Free V/F setting, freq.2
Free V/F setting, voltage.2
Free V/F setting, freq.3
Free V/F setting, voltage.3
Free V/F setting, freq.4
Free V/F setting, voltage.4
Free V/F setting, freq.5
Free V/F setting, voltage.5
Free V/F setting, freq.6
Free V/F setting, voltage.6
Free V/F setting, freq.7
Free V/F setting, voltage.7
Brake control enable
Brake Wait Time for Release
Brake Wait Time for
Acceleration
Brake Wait Time for Stopping
Brake Wait Time for
Confirmation
Brake release freq.
Brake release current
Braking freq. setting
Deceleration overvoltage
suppression enable
Decel. overvolt. suppress level
Decel. overvolt. suppress
const.
Decel. overvolt. suppress
proportional gain
Decel. overvolt. suppress
integral time
"b" Function
Description
Set range, 0 to value of
Set range, 0 to 800V
Set range, value of to
Set range, 0 to 800V
Set range, value of to
Set range, 0 to 800V
Set range, value of to
Set range, 0 to 800V
Set range, value of to
Set range, 0 to 800V
Set range, value of to
Set range, 0 to 800V
Set range, to 400(1000)
Set range, 0 to 800V
Two option codes:
Disable
Enable
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0 to 400(1000)
Set range: 0 to 200% of inverter
rated current
Set range: 0 to 400(1000)
Disabled
Enabled
Enabled with accel.
DC bus voltage of suppression.
Range is:
200V class330 to 395
400V class660 to 790
Accel. rate when b130=02.
Set range: 0.10 to 30.00 sec.
Proportional gain when b130=01.
Range is: 0.00 to 5.00
Integration time when b130=01.
Range is: 0.00 to 150.0
67
Run
Mode
Initial data
Edit
*1
*1
Hz
current
*1
Hz
Defaults
Units
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V
00
-
0.00
Sec
0.00
Sec
0.00
Sec
0.00
Sec
0.00
Sec
Rated
A
0.00
Hz
00
380
V
/760
1.00
sec
0.20
1.0
sec