Hitachi WJ200-001S Quick Reference Manual page 73

Wj200 series
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Func.
Name
Code

Pulse train input/output
scale conversion

PID FBV output
high limit

PID FBV output
low limit

Over-torque/under-torque
selection

Over/under-torque level
(Forward powering mode)

Over/under-torque level
(Reverse regen. mode)

Over/under-torque level
(Reverse powering mode)

Over/under-torque level
(Forward regen. mode)

Signal output mode of
Over/under-torque

Electronic thermal warning
level

Zero speed detection level

Heat sink overheat warning

Communication speed

Modbus address

Communication parity

Communication stop bit
"C" Function
Description
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in  (C047)
Set range is 0.01 to 99.99
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0
to 100%
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
Two option codes:
Over-torque
Under-torque
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Two option codes:
During accel., decel. and
constant speed
During constant speed only
Set range is 0 to 100%
Setting 0 means disabled.
Set range is 0.0 to 100.0Hz
Set range is 0 to 110 C
Eight option codes:
2,400 bps
4,800 bps
9,600 bps
19,200 bps
38,400 bps
57,600 bps
76,800 bps
115,200 bps
Set the address of the inverter on
the network. Range is 1 to 247
Three option codes:
No parity
Even parity
Odd parity
Two option codes:
1 bit
2 bit
71
Run
Defaults
Mode
Initial data
Edit
1.00
100.0
0.0
00
100.
100.
100.
100.
01
90
0.00
100.
05
1.
00
1
Units
%
%
-
%
%
%
%
-
%
Hz
C
baud
bit