Func.
Name
Code
Pulse train input/output
scale conversion
PID FBV output
high limit
PID FBV output
low limit
Over-torque/under-torque
selection
Over/under-torque level
(Forward powering mode)
Over/under-torque level
(Reverse regen. mode)
Over/under-torque level
(Reverse powering mode)
Over/under-torque level
(Forward regen. mode)
Signal output mode of
Over/under-torque
Electronic thermal warning
level
Zero speed detection level
Heat sink overheat warning
Communication speed
Modbus address
Communication parity
Communication stop bit
"C" Function
Description
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in (C047)
Set range is 0.01 to 99.99
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0
to 100%
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
Two option codes:
Over-torque
Under-torque
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Two option codes:
During accel., decel. and
constant speed
During constant speed only
Set range is 0 to 100%
Setting 0 means disabled.
Set range is 0.0 to 100.0Hz
Set range is 0 to 110 C
Eight option codes:
2,400 bps
4,800 bps
9,600 bps
19,200 bps
38,400 bps
57,600 bps
76,800 bps
115,200 bps
Set the address of the inverter on
the network. Range is 1 to 247
Three option codes:
No parity
Even parity
Odd parity
Two option codes:
1 bit
2 bit
71
Run
Defaults
Mode
Initial data
Edit
1.00
100.0
0.0
00
100.
100.
100.
100.
01
90
0.00
100.
05
1.
00
1
Units
%
%
-
%
%
%
%
-
%
Hz
C
baud
bit