Func.
Name
Code
Restart mode after FRS
Automatic carrier frequency
reduction
Dynamic braking usage ratio
Stop mode selection
Cooling fan control
Clear elapsed time of cooling
fan
Initialization target data
Dynamic braking control
(BRD) selection
BRD activation level
BRD resistor value
"b" Function
Description
Selects how the inverter resumes
operation when free-run stop (FRS)
is cancelled, three options:
Restart from 0Hz
Restart from frequency
detected from real speed of
motor (freq. matching)
Restart from frequency
detected from real speed of
motor (active freq. matching)
Three option codes:
Disabled
Enabled, depending on the
output current
Enabled, depending on the
heat-sink temperature
Selects the rate of use (in %) of the
regenerative braking resistor per
100 sec. intervals, range is 0.0 to
100%.
0%: Function disabled
>0%: Enabled, per value
Select how the inverter stops the
motor, two option codes:
DEC (decelerate to stop)
FRS (free-run to stop)
Selects when the fan is ON during
inverter operation, three options:
Fan is always ON
Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
Fan is temperature controlled
Two option codes:
Count
Clear
Select initialized parameters, four
option codes:
All parameters
All parameters except in/output
terminals and communication.
Only registered parameters in
xxx.
All parameters except
registered parameters in xxx
and .
Three option codes:
Disable
Enable during run only
Enable always
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
Min.Resistance to 600.0
66
Run
Defaults
Mode
Initial data
Units
Edit
00
01
-
0.0
%
00
01
-
00
-
00
-
00
-
360/
V
720
Min.
Ohm
Resistance