Func.
Name
Code
DC braking force at start
DC braking time at start
Carrier frequency during DC
braking
Frequency upper limit
Frequency upper limit,
2nd motor
Frequency lower limit
Frequency lower limit,
2nd motor
Jump freq. (center) 1 to 3
Jump freq. width (hysteresis) 1
to 3
Acceleration hold frequency
Acceleration hold time
"A" Function
Description
Level of DC braking force at
start, settable from 0 to 100%
Sets the duration for DC braking,
range
is
seconds
Carrier frequency of DC braking
performance, range is from 2.0 to
15.0kHz
Sets a limit on output frequency
less than the maximum
frequency ().
Range is from frequency lower
limit () to maximum
frequency ().
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
less than the maximum
frequency ().
Range is from frequency lower
limit () to maximum
frequency ().
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency ()
to frequency upper limit ()
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency ()
to frequency upper limit ()
0.0 setting is disabled
>0.0 setting is enabled
Up to 3 output frequencies can
be defined for the output to jump
past to avoid motor resonances
(center frequency)
Range is 0.0 to 400.0(1000)
Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
Sets the frequency to hold
acceleration, range is 0.0 to
400.0(1000)
Sets the duration of acceleration
hold, range is 0.0 to 60.0
seconds
56
from
0.0
to
60.0
*1
Hz
*1
Hz
Run
Defaults
Mode
Initial data
Units
Edit
0.
0.0
sec.
5.0
sec.
0.00
0.00
0.00
0.00
0.0
0.0
0.0
0.5
0.5
0.5
0.00
0.0
sec.
%
Hz
Hz
Hz
Hz
Hz
Hz
Hz