Func.
Name
Code
Function code display
restriction
Initial display selection
Automatic user parameter
registration
Torque limit selection
Torque limit 1 (fwd/power)
Torque limit 3 (rev/power)
Torque limit 4 (fwd/regen.)
Torque LAD STOP selection
Reverse run protection
Dual Rating Selection
Controlled deceleration on
power loss
DC bus voltage trigger level of
ctrl. decel.
Over-voltage threshold of ctrl.
decel.
Deceleration time of ctrl. decel.
Initial freq. drop of ctrl. decel.
"b" Function
Description
Six option codes:
Full display
Function-specific display
User setting (and )
Data comparison display
Basic display
Monitor display only
Func. code that SET key
pressed last displayed.(*)
~~ displayed
displayed
B display of LCD operator
Two option codes:
Disable
Enable
Three option codes:
Quadrant-specific setting mode
Terminal-switching mode
Analog voltage input mode(O)
Torque
limit
powering quadrant, range is 0 to
200%/no(disabled)
Torque
limit
powering quadrant, range is 0 to
200%/no(disabled)
Torque limit level in forward regen.
quadrant,
200%/no(disabled)
Two option codes:
Disable
Enable
Two option codes:
No protection
Reverse rotation is protected
(CT mode) / (VT mode)
Four option codes:
Trips
Decelerates to a stop
Decelerates to a stop with DC
bus voltage controlled
Decelerates to a stop with DC
bus voltage controlled, then
restart
Setting of DC bus voltage to start
controlled decel. operation. Range is
0.0 to 1000.0
Setting the OV-LAD stop level of
controlled decel. operation. Range is
0.0 to 1000.0
Range is 0.01 to 3600.0
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
64
level
in
forward
level
in
reverse
range
is
0
to
Run
Defaults
Mode
Initial data
Units
Edit
00
001
00
00
200
%
200
%
200
%
00
00
00
00
220.0/
V
440.0
360.0/
V
720.0
1.0
sec
0.0
Hz