Func.
Name
Code
[AM] terminal selection
(Analog voltage output
0...10V)
Digital current monitor
reference value
Output [11] active state
Output [12] active state
Alarm relay active state
Output mode of low current
detection
Low current detection level
Output mode of overload
warning
Overload warning level
Overload warning level, 2
motor
Frequency arrival setting
for acceleration
Frequency arrival setting
for deceleration
PID deviation level
Frequency arrival setting 2
for acceleration
Frequency arrival setting 2
for deceleration
"C" Function
Description
11 programmable functions:
Output frequency
Output current
Output torque
Output voltage
Input power
Electronic thermal load ratio
LAD frequency
Heat sink temperature
Output torque (with code)
General output
Option
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
normally open [NO]
normally closed [NC]
Two option codes:
During acceleration,
deceleration and constant speed
During constant speed only
Set the level of low load detection,
range is 0.0 to 2.0 * inverter rated
current
Two option codes:
During accel., decel. and
constant speed
During constant speed only
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
nd
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0(1000)
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0(1000)
Sets the allowable PID loop error
magnitude (absolute value),
SP-PV, range is 0.0 to 100%
Set range is 0.0 to 400.0(1000)
Set range is 0.0 to 400.0(1000)
70
Run
Mode
Edit
Rated current
current
Rated current
Rated current
*1
Hz
*1
Hz
*1
Hz
*1
Hz
Defaults
Initial data
Units
07
[LAD]
A
00
00
-
01
01
Rated
A
01
A
x 1.15
A
x 1.15
0.0
Hz
0.0
Hz
3.0
%
0.00
Hz
0.00
Hz