Func.
Name
Code
PID enable
PID proportional gain
PID integral time constant
PID derivative time constant
PV scale conversion
PV source
Reverse PID action
PID output limit
PID feed forward selection
AVR function select
AVR function select,
nd
2
motor
AVR voltage select
AVR voltage select,
nd
2
motor
AVR filter time constant
AVR deceleration gain
"A" Function
Description
Enables PID function,
three option codes:
PID Disable
PID Enable
PID Enable with reverse
output
Proportional gain has a range of
0.00 to 25.00
Integral time constant has a
range of 0.0 to 3600 seconds
Derivative time constant has a
range of 0.0 to 100 seconds
Process Variable (PV), scale
factor (multiplier), range of 0.01
to 99.99
Selects source of Process
Variable (PV), option codes:
[OI] terminal (current in)
[O] terminal (voltage in)
Modbus network
Pulse train input
Calculate function output
Two option codes:
PID input = SP-PV
PID input = -(SP-PV)
Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
Selects source of feed forward
gain, option codes:
Disabled
[O] terminal (voltage in)
[OI] terminal (current in)
Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
AVR enabled
AVR disabled
AVR enabled except during
deceleration
200V class inverter settings:
200/215/220/230/240
400V class inverter settings:
380/400/415/440/460/480
Define the time constant of the
AVR filter, range is 0 to 10 sec.
Gain adjustment of the braking
performance, range is 50 to
200%
57
Run
Defaults
Mode
Initial data
Units
Edit
00
1.0
1.0
0.00
1.00
00
00
0.0
00
02
02
230/
400
230/
400
0.300
100.
sec
sec
%
V
V
sec
%