Func.
Name
Code

PID enable

PID proportional gain

PID integral time constant

PID derivative time constant

PV scale conversion

PV source

Reverse PID action

PID output limit

PID feed forward selection

AVR function select

AVR function select,
nd
2
motor

AVR voltage select

AVR voltage select,
nd
2
motor

AVR filter time constant

AVR deceleration gain
"A" Function
Description
Enables PID function,
three option codes:
PID Disable
PID Enable
PID Enable with reverse
output
Proportional gain has a range of
0.00 to 25.00
Integral time constant has a
range of 0.0 to 3600 seconds
Derivative time constant has a
range of 0.0 to 100 seconds
Process Variable (PV), scale
factor (multiplier), range of 0.01
to 99.99
Selects source of Process
Variable (PV), option codes:
[OI] terminal (current in)
[O] terminal (voltage in)
Modbus network
Pulse train input
Calculate function output
Two option codes:
PID input = SP-PV
PID input = -(SP-PV)
Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
Selects source of feed forward
gain, option codes:
Disabled
[O] terminal (voltage in)
[OI] terminal (current in)
Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
AVR enabled
AVR disabled
AVR enabled except during
deceleration
200V class inverter settings:
200/215/220/230/240
400V class inverter settings:
380/400/415/440/460/480
Define the time constant of the
AVR filter, range is 0 to 10 sec.
Gain adjustment of the braking
performance, range is 50 to
200%
57
Run
Defaults
Mode
Initial data
Units
Edit
00
1.0
1.0
0.00
1.00
00
00
0.0
00
02
02
230/
400
230/
400
0.300
100.
sec
sec
%
V
V
sec
%

Hide quick links: