Adjustments - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

ii
FIRE
OR EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
injury,
death, and/or property
damage.
Never
purge
a gas line into a combustion
chamber.
Never
test for gas leaks with
an open
flame. Use a commercially
available
soap solution
made specifically
for the detection
of leaks to check
all connections.
A fire or explosion
may
result
causing
property
damage,
personal
injury
or loss of
line.
Adjustments
FIRE
HAZARD
Failure
to follow
this warning
could
result
in personal
injury,
death and/or property
damage.
DO NOT
bottom
out gas valve
regulator
adjusting
screw.
This can result
in unregulated
manifold
pressure
and result
in excess overfire
and heat exchanger
failures.
FURNACE
DAMAGE
HAZARD
Failure
to follow
this caution may result
in reduced
furnace
life.
DO
NOT
redrill
orifices.
Improper
drilling
(burrs,
out-of-round
holes,
etc.) can cause
excessive
burner
noise
and misdirection
of burner
flames.
This can result
in flame
impingement
of heat exchangers,
causing
failures.
(See Fig.
52.)
For proper
operation
and long
term reliability,
the Furnace
input
rate must
be within
+/-2
percent
of input
rate on furnace
rating
plate.
The gas input rate on rating plate is for installations
at altitudes
up
to 2000 ft. (609.6M).
In the USA.,
the input rating
for altitudes
above 2000 ft. (609.6M)
must be reduced
by 2 percent
for each 1000 ft. (304.8M)
above sea
level. Refer to Table 16.
In Canada,
the input
rating
must
be derated
by 5 percent
for
altitudes
of 2000
ft. (609.6M)
to 4500
ft. (1371.6M)
above
sea
level.
To adjust manifold
pressure
to obtain
the proper
input
rate, first,
determine
if the furnace
has the correct
orifice
installed.
At higher
altitudes
or different
gas heat contents,
it may
be necessary
to
change
the factory
orifice
to a different
orifice.
Tables have been
provided
in
the
furnace
installation
instructions
to
match
the
required
orifice
to the manifold
pressure
to the heat content
and
specific gravity
of the gas. To do this:
a. Obtain average yearly gas heat value (at installed
altitude)
from local gas supplier.
b. Obtain
average yearly
gas specific
gravity from local gas
supplier.
c. Find installation
altitude
in Table 19.
d. Find closest natural
gas heat value
and specific
gravity in
Table 19.
e. Follow heat value and specific gravity lines to point of in-
tersection
to find orifice size and low-and
high-heat
mani-
fold pressure
settings
for proper
operation.
f. Check and verify burner
orifice size in furnace.
NEVER
ASSUME
ORIFICE
SIZE.
ALWAYS
CHECK
AND
VERIFY.
NOTE:
For Canadian
altitudes
of 2000
to 4500
ft. (609.6
to
1371.6M),
use
USA
altitudes
of 2001
to 3000
ft. (609.6
to
914.4M).
NOTE:
If orifice hole appears
damaged
or it is suspected
to have
been
redrilled,
check
orifice
hole
with
a numbered
drill bit of
correct
size.
Never
redrill
an orifice.
A burr-free
and squarely
aligned
orifice hole is essential
for proper
flame characteristics.
g. Replace
orifice with correct size, if required
by Table 19.
Use only factory-supplied
orifices.
See EXAMPLE
1.
EXAMPLE
1
EXAMPLE:
0 - 2000 ft. (0 - 609.6M)
altitude
Heating
value = 1050 Btu/cu ft.
Specific
gravity
= 0.62
Therefore:
Orifice No. 44
Manifold
pressure:
3.4-in.
w.c. for high heat,
1.4-in.
w.c. for low
heat
* Furnace
is shipped with No. 44 orifices. In this example,
all main
burner
orifices are the correct size and do not need to be changed
to
obtain
proper
input rate.
1. Adjust
manifold
pressure
to obtain
low fire input
rate. (See
Fig. 51.)
a. Turn gas valve ON/OFF
switch
to OFF.
b. Remove
manifold
pressure
tap plug from gas valve.
c. Connect
a water
column
manometer
or similar
device
to
manifold
pressure
tap.
d. Turn gas valve ON/OFF
switch
to ON.
e. Move setup SWI--2
on furnace control to ON position
to
lock furnace in low-heat
operation.
(See Fig. 55 and Fig.
35.)
f. Manually
close blower
door switch.
g. Jumper
R and W/WI
thermostat
connections
on control to
start furnace.
(See Fig. 35.)
h. Remove
regulator
adjustment
cap from low heat gas valve
pressure
regulator
(See Fig. 51) and turn low-heat
adjust-
ing screw (3/16 or smaller
fiat-tipped
screwdriver)
coun-
terclockwise
(out) to decrease
input rate or clockwise
(in)
to increase
input rate.
NOTE:
DO NOT set low-heat
manifold
pressure
less than 1.3-in.
W.C.
or more
than
1.7-in.
W.C.
for natural
gas.
If manifold
pressure
is outside
this range, change main burner
orifices.
i. Install
low-heat
regulator
adjustment
cap.
j. Move setup switch SW1-2
to offposition
after completing
low-heat
adjustment.
k. Leave manometer
or similar device connected
and proceed
to Step 4.
2. Adjust
manifold
pressure
to obtain high fire input rate. (See
Fig. 51.)
a. Jumper
R to W/WI
and W2 thermostat
connections
on fur-
nace control.
This keeps furnace locked in high-heat
oper-
ation.
b. Remove
regulator
adjustment
cap from
high-heat
gas
valve pressure
regulator
(See Fig. 51) and turn high heat
adjusting
screw
(3/16-in.
or smaller
fiat-tipped
screw-
driver)
counterclockwise
(out) to decrease
input
rate or
clockwise
(in) to increase
input rate.
NOTE:
DO
NOT
set high-heat
manifold
pressure
less
than
3.2-in.
W.C. or more than 3.8 in. W.C. for natural gas.
If manifold
pressure
is outside
this range, change main burner
orifices
to obtain
manifold
pressure
in this range.
62

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents