Direct Vent Termination Clearance - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

................................
/
I
_ V!
f'
/
Item
A
B
C
D
E
F
G
H
Clearance
Description
Canadian
Installation
(1)
U.S. Installation
(2)
Clearance
above grade, veranda,
porch, deck, bah
12 in. (305 ram).
18 in. (457 ram) above roof surface.
12 in. (305 ram)
cony or anticipated
snow level
12 in. (305 ram) for appliances
> t0,000
Btuh (3kW)
9 in. (229 ram) for appliances
> 10,000 Btuh (3kW)
Clearance
to a window
or door that may be opened
and </-
100,000 Btuh (30 kW), 36 in. (914 ram) for
and </-
50,000 Btuh (15 kW), 12 in. (305 ram) for
appliances
> 100,000 Btuh (30 kW)
appliances
> 500,000
Btuh (15 kW)
Clearance
to a permanently
closed window
Vertical clearance
to a ventilated
soffit located above
the terminal within a horizontal
distance
of 2 feet (61
cm) from the centerline
of the terminal
Clearance
to an unventilated
soffit
Clearance
to an outside
corner
Clearance
to an inside corner
Clearance
to each side of the centerline
extended
above electrical
meter or gas service regulator
as-
sembly
Clearance
to service regulator
vent outlet
Clearance
to non-mechanical
air supply inlet to
building
or the combustion
air inlet to any other applb
ance
Clearance
to a mechanical
air supply
inlet
For clearances
not specified
in ANSI Z223.1/NFPA
54
or CSA B149.1, clearances
shall be in accordance
with local installation
codes and the requirements
of
the gas supplier
and the manufacturer's
installation
instructions.
For clearances
not specified
in ANSI Z223.1/NFPA
54
or CSA B149.1, clearances
shall be in accordance
with local installation
codes and the requirements
of
the gas supplier
and the manufacturer's
installation
instructions.
3 ft. (.9 M) within 15 ff. (4.6 M) above the meter/
3 ft. (.9 M) within 15 ff. (4.6 M) above the meter/
regulator
assembly
regulator
assembly
3 ff. (.9 M)
12 in. (305 ram) for appliances
> t0,000
Btuh(3kW)
and </-
100,000 Btuh (30 kW), 36 in. (914 ram) for
appliances
> 100,000 Btuh (30 kW)
5 ft. (1.8 M)
J
K
12 in. (305 ram).
Permitted
onty if veranda,
porch,
L
Clearance
under a veranda,
porch, deck, or balcony
deck, or balcony is fully open on a minimum
of two
sides beneath the floor.
Clearance
to each side of the centerline
extended
above or below vent terminal of the furnace to a dryer
M
or water heater vent, or other appliance's
direct vent
12 in. (305 ram)
12 in. (305 ram)
intake or exhaust
Clearance
to the vent terminal
of a dryer vent, water
N
heater vent, or other appliances
direct vent intake or
3 ft. (.9 M)
3 ft. (.9 M)
exhaust
O
Clearance
from a plumbing
vent stack
3 ft. (.9 M)
3 ft. (.9 M)
For clearances
not specified
in ANSI Z223.1/NFPA
54
7 ft. (2.1 M). A vent shall not terminate
above a side-
or CSA B149.1, clearances
shall be in accordance
p
Clearance
above
paved sidewalk or paved driveway
walk or paved driveway
that is located between
two
with local installation
codes and the requirements
of
located
on public property
single family dwellings
and serves both dwellings,
the gas supplier
and the manufacturer's
installation
instructions.
(1) In accordance
with the current CSA B149.1, Natural Gas and Propane Installation
Code.
(2) In accordance
with the current ANSI Z223.1 .NFI'A 54, National Fuel (;as Code
Notes:
1. The vent Iklr this appliance
stiall not terminate:
a. Overpub[icwa[kways:
lit
*3 ft. (.9 M) *For clearances
not specified
in ANSI Z223.1
/NFPA 54or CSA B149.1, clearances
shall be in
accordance
with local installation
codes and the
requirements
of the gas supplier
and the manufacturer's
installation
instructions.
9 in. (229 ram) for appliances
> 10,000 Btuh (3kW)
and </-
50,000 Btuh (15 kW), 12 in. (305 ram) for
appliances
> 500,000
Btuh (15 kW)
3 ff. (.9 M)
For clearances
not specified
in ANSI Z223.1/NFPA
54
or CSA B149.1, clearances
shall be in accordance
with local installation
codes and the requirements
of
the gas supplier
and the manufacturer's
installation
instructions.
b.
Near
so,it
vents
of crawl
space
vents
or ottier
areas wtiere
condensa_
or vapor
could
create a nuisance
or hazard
or property
damage;
or
c. Where
condensate
vapor
could
cause damage
or could
be de_imental
to the operation
of regula_lrs,
relief
valves,
or other
equipment.
2.
When
locating
vent
terminations,
consideration
must
be given
to prevailing
winds,
location,
and
other
conditions
which
may
cause
recirculadon
of the
combustion
products
of adjacent
vents.
Recirculadon
can cause
poor combustion,
inlet
condensate
problems,
and accelerated
co_oshm
of the heat exchangers.
3.
Avoid
venting
under
a deck
or large overhang.
Recirculation
could
occur
and cause
per_lrmance
or system
problems.
Al1046
Fig. 45 - Direct Vent Termination
Clearance
56

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents