Condensate Drain Connection - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

H
CONDENSATE
DRAIN CONNECTION
FROZEN
AND BURST
WATER
PIPE HAZARD
Failure
to protect
against the risk of freezing
may
result
in
property
damage.
Special
precautions
MUST
be made if installing
furnace
in an
area which
may drop below freezing.
This can cause improper
operation
or damage
to equipment.
If furnace
environment
has the potential
of freezing,
the drain trap and drain line must
be protected.
The use of electric
heat tape or RV antifreeze is
recommended
for these installations.
PROPERTY
DAMAGE
HAZARD
Failure
to follow
this caution may result
in burst water pipes
and/or property
damage.
If a condensate
pump is installed,
a plugged
condensate
drain
or a failed pump may cause the furnace
to shut down.
Do not
leave the home
unattended
during
freezing
weather
without
turning
off water supply and draining
water pipes or otherwise
protecting
against the risk of frozen pipes.
DO NOT
trap the drain
line
in any other
location
than at the
condensate
drain
trap supplied
with
the furnace.
If possible,
DO
NOT route the drain line where
it may freeze.
The drain line must
terminate
at an inside
drain to prevent
freezing
of the condensate
and possible
property
damage.
Special
precautions
MUST
be made if installing
furnace in an area
which
may
drop
below
freezing.
This
can
cause
improper
operation
or damage
to the equipment.
If the furnace
environment
has the potential
of freezing,
the drain trap and drain line must be
protected.
A self-regulating,
shielded
and waterproof
heat tape
rated at 3 to 6 watt per foot at 115 volt, 40°F (4°C)
may be used
to help provide
freeze protection.
Wrap
the drain trap and drain
line with
the heat tape and secure with
the ties.
Follow
the heat
tape
manufacturer's
recommendations.
Prime
the
trap before
furnace
operation.
Upflow/Downflow
Orientation
In the Upflow
or Downflow
orientation,
the condensate
trap is
inside
the furnace
casing.
The condensate
drain
must
be routed
from the trap through
the furnace
casing.
The condensate
drain can
be routed
through
the left or right side of the casing.
(The left or
right side is as you are viewing/facing
the furnace
from
the front.)
The
furnace
condensate
drain
can
be
connected
to
the
Air
Conditioning
condensate
drain as shown
in Fig. 13.
NOTE:
On
narrower
casings,
it may
be easier
to remove
the
condensate
trap,
connect
the drain
line components
and re-install
the
condensate
trap.
Read
the
steps
thoroughly
to
familiarize
yourself
with the required
steps.
For
Right
Side
Condensate
Drain:
1. Remove
the 7/8-in.
knock-out
from the right side of the
casing.
(See Fig. 12 .)
2. Remove
the pre-formed
rubber drain elbow
and two spring
clamps from the loose parts bag.
3. Slide
a spring
clamp
1 inch (25 mm) down
the plain end
(the end without
the formed
grommet)
of the drain elbow.
4. From
inside the casing,
insert
the formed
grommet
end of
the elbow through
the 7/8-in.
knockout
in the casing.
5. Pull the grommet
through
the casing from the outside
until
it is seated
in the knockout
6. Attach
the plain end of the drain elbow to the outlet stub on
the drain
trap.
Secure
the drain
tube to the trap with
the
spring clamp.
The remaining
drain line can be constructed
from
field supplied
l/2-in.
CPVC
or 3/4-in.
PVC
pipe,
in compliance
with
local
building
codes. A factory-supplied
l/2-in.
CPVC
to 3/4-in.
PVC
adapter
is supplied
in the loose parts bag for use as required.
7. Install
the adapter
or connect
the l/2-in.
CPVC
pipe
by
sliding
a spring clamp over the open end of the grommet
on
the outside
the furnace
casing.
8. Open
the
spring
clamp
and
insert
the
long
end
of the
adapter
or the l/2-in.
CPVC
pipe into the outlet stub on the
drain tube.
9. Connect
additional
condensate
piping
to a code-approved
drain, or to a condensate
pump approved
for use with acidic
furnace
condensate
and
compatible
with
mineral
and
vegetable
oils, such as canola oil.
Allow
at least
l/4-in.
(6 mm)
per foot
of slope
away from
the
furnace
in horizontal
sections
of drain line.
For
Left
Side
Condensate
Drain
Connection:
1. For left side condensate
drainage,
the drain
line is routed
from
the condensate
trap, behind
the inducer
(upflow)
or
gas valve (downflow)
and out through
the left side of the
furnace
casing.
A pre-formed
l/2-in.
CPVC
"Z-pipe"
is
provided
with
the furnace.
The Z-pipe
is long
enough
to
extend across the casing for drain connections.
2. The Z-pipe
is connected
to the condensate
trap and the
outside
of the
furnace
by modifying
the formed
rubber
drain elbow
as shown
in Fig. 17.
3. Locate the Z-pipe.
Remove
the pre-formed
drain elbow and
four spring
clamps from the loose parts bag.
4. Remove
the formed
grommet
from the rubber
drain elbow
by cutting
the elbow
along
the vertical
line located
about
1-3/8 in. (35 mm) away from the formed
grommet.
See Fig.
15. DO NOT DISCARD
THE FORMED
GROMMET
OR
THE RUBBER
ELBOW.
Both of these pieces will be used.
Assemble
and route
the
drain
line
to the opposite
side
of the
furnace
as detailed
below:
5. Remove
the knock-out
from the left side of the casing.
(See
Fig. 12.)
6. From the outside
of the casing,
insert the angled end of the
Z-pipe through
drain hole in the side left of the casing and
behind
the
inducer
or gas
valve.
Allow
the
Z-pipe
to
temporarily
rest on the blower
shelf (upflow)
or burner
box
(downflow).
7. After inserting
the Z pipe through
the casing,
slide a spring
clamp over each end of the Z pipe.
8. From inside
the casing,
insert
the short end of the formed
grommet
cut
from
the
rubber
drain
elbow
through
the
7/8-in.
drain knockout
in the casing.
9. Pull the grommet
through
the casing
from the outside
until
it is seated in the knockout.
10. Align
the Z-pipe
with the long
end of the grommet
inside
the furnace
and insert slightly.
The angled end of the tube at
the other side of the casing should be facing the front of the
furnace.
11. Slide a spring
clamp
over the end of the remaining
rubber
drain elbow.
12. Attach
the drain elbow to the angled end of Z-pipe
and the
drain trap outlet
stub. Adjust
the length
of Z-pipe
inserted
into the grommet
at the
opposite
side
of the furnace
as
necessary
for proper
fit and positioning.
In both upflow
and
downflow
orientations,
the Z-pipe
should
NOT
be resting
on any sheet metal parts.
16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents