Knockout Removal; Example Of Field Drain Attachment - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

13. S ecure the rubber elbow tothe drain trap and theZ-pipe
with spring c lamps.
14. S ecure the grommet
tothe Z-pipe with the spring c lamp.
The remaining
drain linecan beconstructed
from fieldsupplied
l/2-in.CPVC or 3/4-in. P VC pipe, i n compliance
withlocal
building codes. A factory-supplied
l/2-in.CPVC to3/4-in. PVC
adapter
issupplied inthe loose p arts bag foruse as required.
15. I nstall theadapter orconnect thel/2-in.CPVC pipe by
sliding a spring c lamp over the open e nd ofthe grommet
on
the outside the furnace casing.
16. O pen thespring clamp and insert t helongendof the
adapter
orthe l/2-in. C PVC pipe into the outlet stub o nthe
drain t ube.
17. C onnect additional condensate
piping toacode-approved
drain, ortoacondensate
pump a pproved
foruse withacidic
furnace c ondensate
andcompatible with mineral and
vegetable
oils, s uch a s canola oil.
Allow at least l/4-in. (6 mm) per foot of slope away from the fur-
nace in horizontal sections of drain line.
Horizontal
Orientation
1. In the
Horizontal
orientation,
a field supplied
accessory
drain trap grommet
is required
to seal the gap between
the
casing
and the condensate
trap for direct vent applications,
only. The grommet
is NOT required
for single-pipe,
or oth-
er non-direct-vent
applications.
2. The condensate
trap outlet extends
2 in. (51 ram) below the
furnace
casing.
To
allow
for
servicing
the
trap,
the
condensate
drain tube in the loose parts bag can be modified
to
make
a coupler
to
allow
for
future
service
of the
condensate
trap and drain line.
3. Remove
the knock-out
for the condensate
trap in the side of
the casing.
4. Install
the drain trap grommet
in the casing
if required
for
direct vent applications.
If necessary,
remove
the trap, install
the grommet
and re-install
the trap.
5. Remove
the pre-formed
rubber
drain elbow, and two spring
clamps from the loose parts bag.
6. Remove
the formed
grommet
on the elbow
to create
an
elbow or straight
connector.
(See Fig. 15.)
7. Connect
the
cut elbow
or grommet
to the outlet
of the
condensate
trap with 1 spring
clamp.
The remaining
drain
line can be constructed
from field-supplied
l/2-in.
CPVC or 3/4-in.
PVC
pipe, in compliance
with local build-
ing codes. A factory-supplied
l/2-in.
CPVC to 3/4-in.
PVC adapter
is supplied
in the loose parts bag for use as required.
8. Install
the adapter
or connect
the l/2-in.
CPVC
pipe by
sliding
a spring
clamp
over
the open
end of the elbow
or
grommet
on the outside
the furnace casing.
9. Open
the
spring
clamp
and insert
the long
end
of the
adapter
or the 1/2-in.
CPVC
pipe into the outlet stub on the
drain tube.
10. Connect
additional
condensate
piping
to a code-approved
drain, or to a condensate
pump approved
for use with acidic
furnace
condensate
and
compatible
with
mineral
and
vegetable
oils, such as canola oil.
Allow
at least
1/4-in.
(6 ram) per foot of slope
away from
the
furnace
in horizontal
sections
of drain line.
CUT HAZARD
Failure to follow this caution may result in personal iniury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
Fig. 12 - Knockout
Removal
OPEN STAND
PiPE FOR
A/C OR
HUMIDIFIER
DRAIN
U
_T----TE E
TO OPEN
DRAIN
Fig. 13 - Example
of Field Drain
Attachment
Al1276
H
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents