Electrical Connections; 115-V Wiring; Maximum Capacity Of Pipe; Gas Entry - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

H
Table
8 - Maximum
Capacity
of Pipe
NOMINAL
LENGTH
OF PIPE
- FT (M)
IRON
PIPE
SIZE
10
20
30
40
50
IN. (MM)
(3.0)
(6.0)
(9.1)
(12.1)
(15.2)
1/2 (13)
175
120
97
82
73
3/4 (19)
350
250
200
170
151
1 (25)
580
455
375
320
285
1-1/4
(32)
1400
950
770
550
580
1-1/2
(39)
21 O0
1450
1180
990
900
* Cubic
ft of gas per hr for gas pressures
of 0.5 psig
(14- In. W.C.) or less and
a pressure
drop
of 0.5-In.
W.C. (based
on a 0.60
specific
gravity
gas).
Ref:
Table 8 above
and 6.2 of NFPA54/ANSl
Z223.1-2009.
Left Side Gas Entry. Gas Pipe
Grommet Required For Direct
Vent Applications.
Gas Pipe Grommet Required
For Direct Vent Applications
Fig. 29 - Gas Entry
I
Al1338
MANUAL
,._
SHUTOFF
[
VALVE
(REQUIRED)
J
SEDIMENT
TRAP
UNION
_
\
FRONT
/
/
NOTE: Union may be inside the
vestibule where permitted by
local codes.
Fig. 30 - Typical
Gas Pipe Arrangement
ELECTRICAL
CONNECTIONS
Al1035
Field-supplied
wiring
shall conform
with
the limitations
of 63°F
33 ° C) rise.
ELECTRICAL
SHOCK
AND FIRE
HAZARD
Failure
to follow
this
warning
could
result
in personal
injury, death, or property
damage.
The
cabinet
MUST
have
an uninterrupted
or unbroken
ground
according
to NEC
ANSI/NFPA
70-2011
or local
codes
to minimize
personal
injury
if an electrical
fault
should
occur. In Canada,
refer to Canadian
Electrical
Code
CSA
C22.1.
This
may consist
of electrical
wire, conduit
approved
for electrical
ground
or a listed, grounded
power
cord
(where
permitted
by
local
code)
when
installed
in
accordance
with
existing
electrical
codes.
Refer
to the
power
cord
manufacturer's
ratings
for proper
wire
gauge.
Do not use gas piping as an electrical
ground.
FURNACE
MAY NOT OPERATE
HAZARD
Failure to follow this caution may result in intermittent
furnace operation.
Furnace control must be grounded for proper operation or
else control will lock out. Control nmst remain grounded
through green/yellow wire routed to gas valve and manifold
bracket screw.
l15-V
Wiring
Furnace
must have a l15-v
power
supply
properly
connected
and
grounded.
NOTE:
Proper
polarity
must
be maintained
for 115-v wiring.
If
polarity
is incorrect,
control
LED
status indicator
light will flash
rapidly
and furnace
will NOT
operate.
Verify
that the voltage,
frequency,
and phase
correspond
to that
specified
on unit rating
plate.
Also, check
to be sure that service
provided
by utility
is sufficient
to handle
load imposed
by this
equipment.
Refer to rating plate or Table 9 for equipment
electrical
specifications.
U.S.A.
Installations:
Make all electrical connections
in accordance
with
the current
edition
of the National
Electrical
Code
(NEC)
ANSI/NFPA
70 and any
local
codes
or ordinances
that
might
apply.
Canada
Installations:
Make
all
electrical
connections
in
accordance
with
the current
edition
of the Canadian
Electrical
Code
CSA
C22.1
and any local
codes
or ordinances
that might
apply.
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning could result in personal
iniury or death.
Blower door switch opens 115-v power to control. No
component operation can occur. Do not bypass or close
switch with blower door removed.
See Fig. 34 for field wiring diagram showing typical field 115-v
wiring. Check all factory and field electrical connections
for
tightness.
FIRE HAZARD
Failure to follow this warning could result in personal
iniury, death, or property damage.
Do not connect aluminum wire between disconnect
switch and furnace. Use only copper wire. See Fig. 32.
Use a separate,
fused branch
electrical
circuit with a properly
sized
fuse or circuit
breaker
for this furnace.
See Table
9 for wire
size
and fuse specifications.
A readily
accessible
means
of electrical
disconnect
must be located
within sight of the furnace.
32

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents