NOTE:
Maximum
Equivalent
Vent Length
(MEVL)
includes
standard
and concentric
vent termination
and does NOT
include
elbows.
Use Table 14 - Deductions
from
Maximum
Equivalent
Vent Length
to determine
allowable
vent length
for each application.
Altitude
FT (M) 5
Unit Size
40,000
50,000
4501
to 5000
(1370
to
80,000
1524)
100,000
120,000
40,000
50,000
5001
to 8000
80,000
(1524
to
100,000
1829)
120,000
40,000
50,000
8001
to 7000
80,000
(1829
to
100,000
2134)
120,000
40,000
50,000
7001
to 8000
80,000
(2134
to
100,000
2438)
120,000
40,000
50,000
8001
to 9000
80,000
(2438
to
100,000
2743)
120,000
40,000
9001
to
50,000
10,000
80,000
(2743
to
100,000
3048)
120,000
Table 15 - Maximum
Equivalent
Vent Length
- Ft. (M)
4501 to 10,000
Ft. (1371 to 3048 M) Altitude
DIRECT VENT (2-PIPE) AND SINGLE-PIPE
Vent Pipe Diameter (in.) 1
1-1/2
2
2-1/2
3
NOTES:
1. Use only the vent pipe sizes shown for each furnace.
It is NOT necessary
to choose the smallest diameter
pipe possible for venting.
2. NA - Not allowed.
Pressure switch will not close, or flame disturbance
may result.
3. Total equivalent
vent lengths under 10' for 40,000 BTUH furnaces from 0 to 2000 ft. (0 to 610 M) above sea level
require use of an outlet choke plate.
Failure to use an outlet
choke when required
may result
in flame disturbance
or flame
sense lockout.
4. Not all furnace families include 140,000 BTUH input models.
5. Vent sizing for Canadian
installations
over 4500 It (1370 M) above sea level are subject to acceptance
by local authorities
having jurisdiction.
6. Size both the combustion
air and vent pipe independently,
then use the larger size for both pipes.
7. Assume the two 45 ° elbows equal one 90 ° elbow. Wide radius elbows are desirable
and may be required in some cases.
8. Elbow and pipe sections within the furnace casing and at the vent termination
should
not be included
in vent length or elbow count.
9. The minimum
pipe length is 5 ft. (1.5 M) linear feet (meters) for all applications.
10. Use 3-in.
(76 mm) diameter vent termination
kit for installations
requiring
4-in.
(102 mm) diameter
pipe.