Sequence Operation; Two-Stage Heating (Adaptive Mode) With Single-Stage Thermostat - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

SEQUENCE
OF OPERATION
NOTE:
Furnace
control must be grounded
for proper
operation
or
else
control
will
lock
out.
Control
is
grounded
through
green/yellow
wire routed
to gas valve and burner box screw. Using
the schematic
diagram
in Fig. 64, follow
the sequence
of operation
through
the different
modes.
Read and follow
the wiring
diagram
very carefully.
NOTE:
If a power
interruption
occurs
during
a call for heat
(W/Wl
or
W/Wl-and-W2),
the
control
will
start
a 90-sec
blower-only
ON period
two
sec after power
is restored,
if the
thermostat is still calling for gas heating.
The amber LED light will
flash code 12 during
the 90-sec
period,
after which
the LED will
be ON continuous,
as long
as no faults
are detected.
After the
90-sec
period,
the furnace
will respond
to the thermostat
normally.
The blower
door
must
be installed
for power
to be conducted
through
the blower
door
interlock
switch
ILK
to the
furnace
control
CPU,
transformer
TRAN,
inducer
motor
IDM,
blower
motor BLWM,
hot-surface
igniter HSI, and gas valve GV.
1. Two-Stage
Heating
(Adaptive
Mode)
with Single-Stage
Thermostat
See Fig.
35 and 36 for thermostat connections
NOTE:
The
low-heat
only
switch
SWI-2
selects
either
the
low-heat
only operation
mode
when
ON, (see item 2. below)
or
the adaptive
heating
mode when OFF in response
to a call for heat.
(See Fig. 55.) When the W2 thermostat
terminal
is energized
it will
always
cause
high-heat
operation
when
the R-to-W
circuit
is
closed,
regardless
of the setting of the low-heat
only switch.
This
furnace
can operate
as a two-stage
furnace
with
a single-stage
thermostat
because
the
furnace
control
CPU
includes
a
programmed
adaptive
sequence
of controlled
operation,
which
selects
low-heat
or high-heat
operation.
This
selection
is based
upon
the stored
history
of the length
of previous
gas-heating
periods
of the single-stage
thermostat.
The furnace
will start up in either low-
or high-heat.
If the furnace
starts up in low-heat,
the control
CPU
determines
the low-heat
on-time
(from
0
to
16
minutes)
which
is permitted
before
switching
to high-heat.
If the power
is interrupted,
the stored
history
is erased
and the
control
CPU will select low-heat
for up to 16 minutes
and then
switch to high-heat,
as long as the thermostat
continues
to call for
heat.
Subsequent
selection
is based
on
stored
history
of the
thermostat
cycle times.
The wall thermostat
"calls
for heat",
closing
the R-to-W
circuit.
The furnace
control
performs
a self-check,
verifies
the low-heat
and high-heat
pressure
switch contacts
LPS and HPS are open,
and
starts the inducer
motor IDM in high-speed.
a. Inducer
Prepurge
Period
(1.)
If the furnace control
CPU selects low-heat
opera-
tion the inducer
motor IDM comes up to speed, the
low-heat
pressure
switch
LPS closes, and the fur-
nace control
CPU begins
a 15-sec
prepurge
period.
If the low-heat
pressure
switch LPS fails to remain
closed the inducer
motor IDM will remain
running
at high-speed.
After the low-heat
pressure
switch
re-closes
the furnace
control
CPU will begin
a
15-sec
prepurge
period,
and continue
to run the
inducer
motor IDM at high-speed.
(20 If the furnace
control
CPU selects high-heat
opera-
tion, the inducer
motor IDM remains
running
at
high-speed,
and the high-heat
pressure
switch re-
lay HPSR
is de-energized
to close the NC contact.
When sufficient
pressure
is available
the high-heat
pressure
switch
HPS closes, and the high-heat
gas
valve solenoid
GV-HI
is energized.
The furnace
control
CPU begins
a 15-sec
prepurge
period
after
the low-heat
pressure
switch LPS closes. If the
81
high-heat
pressure
switch HPS fails to close and
the low-heat
pressure
switch
LPS closes, the fur-
nace will operate
at low-heat
gas flow rate until the
high-heat
pressure
switch closes for a maximum
of
2 minutes
after ignition.
b. Igniter
Warm-Up
-At the end of the prepurge
period, the
Hot-Surface
Igniter HSI is energized
for a 17-sec
igniter
warm-up
period.
c. Trial-For-Ignition
Sequence
-When
the igniter warm-
up period
is completed
the main gas valve relay contact
GVR closes to energize the gas valve solenoid
GV-M.
The
gas valve solenoid
GV-M
permits gas flow to the burners
where
it is ignited
by the HSI. Five sec after the GVR
closes,
a 2-sec flame proving
period begins.
The HSI ig-
niter will remain energized
until the flame is sensed or until
the 2-sec flame proving
period begins. If the furnace con-
trol CPU selects
high-heat
operation,
the high-heat
gas
valve solenoid
GV-HI
is also energized.
d. Flame-Proving
- When the burner
flame is proved
at the
flame-proving
sensor
electrode
FSE, the inducer
motor
IDM switches
to low-speed
unless the furnace is operating
in high-heat,
and the furnace
control
CPU
begins
the
blower-ON
delay
period
and continues
to hold the gas
valve GV-M
open. If the burner flame is not proved within
two sec, the control
CPU will close the gas valve GV-M,
and the control
CPU will repeat the ignition
sequence
for
up to three more Trials-For-Ignition
before going to Igni-
tion-Lockout.
Lockout
will be reset automatically
after
three hours, or by momentarily
interrupting
115 v ac power
to the furnace,
or by interrupting
24 vac power at SECI
or
SEC2 to the furnace control CPU (not at W/WI,
G, R, etc.).
If flame is proved
when flame should not be present,
the
furnace
control CPU will lock out of Gas-Heating
mode
and operate
the inducer
motor IDM on high
speed until
flame is no longer
proved.
e. Blower-On
delay
- If the burner
flame is proven
the
blower-ON
delays for low-heat
and high-heat
are as fol-
lows:
Low-heat
- 45 sec after the gas valve GV-M
is opened
the blower
motor BLWM is turned ON at low-heat
airflow.
High-heat
- 25 sec after the gas valve GV-M
is opened
the BLWM
is turned
ON at high-heat
airflow. Simultan-
eously,
the humidifier
terminal
HUM
and electronic
air
cleaner
terminal
EAC-1
are energized
and remain
ener-
gized throughout
the heating
cycle.
f. Switching
from Low-
to High-Heat
- If the furnace con-
trol CPU switches
from low-heat
to high-heat,
the furnace
control
CPU will switch
the inducer
motor
IDM
speed
from
low to high.
The high-heat
pressure
switch
relay
HPSR is de-energized
to close the NC contact. When suffi-
cient
pressure
is available
the high-heat
pressure
switch
HPS closes, and the high-heat
gas valve solenoid
GV-HI
is energized.
The blower
motor BLWM
will transition
to
high-heat
airflow
five sec after the furnace
control
CPU
switches
from low-heat
to high-heat.
g. Switching
from High-
to Low-Heat
-The
furnace con-
trol CPU will not switch from high-heat
to low-heat
while
the thermostat
R-to-W
circuit
is closed
when
using
a
single-stage
thermostat.
h. Blower-OffDelay
-When
the thermostat
is satisfied,
the
R to W circuit is opened,
de-energizing
the gas valve GV-
M, stopping
gas flow to the burners,
and de-energizing
the
humidifier
terminal
HUM. The inducer motor IDM will re-
main
energized
for
a 15-sec
post-purge
period.
The
blower
motor BLWM and air cleaner terminal
EAC- 1 will
remain
energized
at low-heat
airflow or transition
to low-
heat airflow for 90, 120, 150, or 180 sec (depending
on se-
ii

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents