Adjustments - Carrier N92MSN Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage, 35-in. (889 mm) tall, 4-way multipoise high efficiency condensing gas furnace
Table of Contents

Advertisement

N92MSN: Installation, Start-up, Operating and Service and Maintenance Instructions
Prime Condensate Trap with Water
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow these warnings could result in personal injury or
death.
Failure to use a properly configured trap or NOT water-priming trap
before operating furnace may allow positive pressure vent gases to
enter the structure through drain tube. Vent gases contain carbon
monoxide which is tasteless and odorless.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation
or performance satisfaction.
Condensate trap must be PRIMED or proper draining may not occur.
The condensate trap has two internal chambers which can ONLY be
primed by pouring water into the inducer drain side of condensate trap.
1. Remove upper and middle collector box drain plugs opposite of the
condensate trap. See
Fig.
62.
Fig. 62 – Priming Condensate Trap
2. Connect field-supplied 5/8-in. (16 mm) ID tube with attached
funnel to upper collector box drain connection.
3. Pour one quart (liter) of water into funnel/tube. Water should run
through collector box, overfill condensate trap, and flow into open
field drain.
4. Remove funnel; replace collector box drain plug.
5. Connect field-supplied 5/8-in. (16 mm) ID tube to middle collector
box drain port.
6. Pour one quart (liter) of water into funnel/tube. Water should run
through collector box, overfill condensate trap, and flow into open
field drain.
7. Remove funnel and tube from collector box and replace collector
box drain plug.
Purge Gas Lines
If not previously done, purge the lines after all connections have been
made and check for
leaks.Table 26
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.

ADJUSTMENTS

FIRE HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw. This can
result in unregulated manifold pressure and result in excess overfire and
heat exchanger failures.
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes,
etc.) can cause excessive burner noise and misdirection of burner
flames. This can result in flame impingement of heat exchangers,
causing failures. See
A11392
If orifice hole appears damaged or it is suspected to have been redrilled,
check orifice hole with a numbered drill bit of correct size. Never
redrill an orifice. A burr-free and squarely aligned orifice hole is
essential for proper flame characteristics.
For proper operation and long term reliability, the Furnace input rate
must be within +/-2 percent of input rate on furnace rating plate, or as
adjusted for altitude.
The gas input rate on rating plate is for installations at altitudes up to
2000 ft. (609.6M).
54
WARNING
!
WARNING
!
CAUTION
!
Fig.
63.
BURNER
ORIFICE
A93059
Fig. 63 – Orifice Hole
NOTICE
!
A93059

Advertisement

Table of Contents
loading

Table of Contents