Configure The Furnace; Install The Vent And Combustion Air Pipe; Installing The Vent Pipe Adapter And Combustion Air Pipe Adapter; Optional Installation Of The Vent Pipe - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

NOTE: Pipe length (ft. / M) specified for maximum pipe lengths
located in unconditioned spaces cannot exceed total allowable pipe
length as calculated from Table 13 or 15.
Configure
the Furnace
CARBON
MONOXIDE
POISONING
HAZARD
Failure to follow this warning
could result in personal
iniury or death.
To route the vent pipe and combustion air pipe through the
furnace, the manufacturer supplied kit must be used. Failure
to properly seal the blower compartment from the furnace
vestibule could result in the circulation of carbon monoxide
throughout the structure. The vent pipe and combustion air
pipe must be a continuous pipe while passing through the
blower compartment.
Seals supplied in this kit must be
installed
per
the
instructions
provided.
Follow
all
procedures outlined in these instructions.
Install
the Vent and Combustion
Air Pipe
With the furnace installed in the required position, remove the
desired knockouts from the casing. It will be necessary to remove
one knockout for the vent pipe and the other knockout for the
combustion air connection. (See Fig. 12.)
Use a fiat blade screwdriver and tap on the knockout on opposite
sides, where the knockout meets the casing. Fold the knockout
down with duct pliers and work the knockout back and forth until
it is removed. Trim any excess metal from the knockout with tin
snips.
The vent elbow can be rotated to the required location on the
casing if necessary. See Fig. 38. To rotate the vent elbow:
1. Loosen the clamp on the inlet of the vent elbow attached to
the inducer.
2. Rotate the vent elbow to the required position. There are
rounded notches in the vent elbow to align it with the
inducer housing for each orientation.
3. Tighten the clamp around the vent elbow. Torque the clamp
to 15 lb-in. See Fig, 39-42.
Installing
the Vent Pipe Adapter
and Combustion
Air
Pipe Adapter
CARBON
MONOXIDE
POISONING
HAZARD
Failure to follow this warning
could result in personal
iniury or death.
To route the vent pipe and combustion air pipe through the
furnace, the manufacturer supplied kit must be used. Failure
to properly seal the blower compartment from the furnace
vestibule could result in the circulation of carbon monoxide
throughout the structure. The vent pipe and combustion air
pipe must be a continuous pipe while passing through the
blower compartment.
Seals supplied in this kit must be
installed
per
the
instructions
provided.
Follow
all
procedures outlined in these instructions.
NOTE:
The rubber
coupling
that attaches
to the vent pipe adapter
must be used.
The adapter
seals the vent pipe to the casing
and
reduces
the strain on the vent elbow attached
to the inducer.
1, Apply
the gaskets
to the vent pipe and combustion
air pipe
adapters,
See Fig. 3%
NOTE:
The vent pipe adapter
has a larger ID than the combustion
air pipe adapter.
2. Align the screw holes in the plastic vent pipe adapter with
the dimples in the casing.
3. Pilot drill the screw holes for the adapter in the casing and
attach the vent pipe adapter to the furnace with sheet metal
screws
4. Slide the end of the rubber vent coupling with notches in it
over the standoffs on the vent pipe adapter.
5. Insert a length of vent pipe through the coupling into the
outlet of the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow.
Torque the clamp to 15 lb-in.
Install the remaining vent and combustion
air pipes as shown
below. It is recommended
that all pipes be cut, prepared, and
preassembled before pem_anently cementing any joint.
1. Working from furnace to outside, cut pipe to required
length(s).
2. Deburr inside and outside of pipe.
3. Chamfer outside edge of pipe for better distribution
of
primer and cement.
4. Clean and dry all surfaces to be joined.
5. Check dry fit of pipe and mark insertion depth on pipe.
6. Insert the vent pipe into the vent elbow.
7. Torque clamp on vent elbow 15 lb-in.
8. Torque clamp on vent coupling 15 lb-in.
9. Insert the combustion air pipe into the adapter.
10. Pilot drill a screw hole through the adapter into the combus-
tion air pipe and secure the pipe to the adapter with sheet
metal screws.
11. Seal around the combustion
air pipe with silicone or foil
tape.
12. After pipes have been cut and preassembled, apply generous
layer of cement primer to pipe fitting socket and end of pipe
to insertion mark. Quickly apply approved cement to end of
pipe and fitting socket (over primer). Apply cement in a
light, uniform coat on inside of socket to prevent buildup of
excess cement. Apply second coat.
13. While cement is still wet, twist pipe into socket with 1/4-in.
turn. Be sure pipe is fully inserted into fitting socket.
14. Wipe excess cement from joint. A continuous bead of ce-
ment will be visible around perimeter of a properly made
joint.
15. Handle pipe joints carefully until cement sets.
16. Horizontal portions of the venting system shall be suppor-
ted to prevent sagging. Support combustion air piping and
vent piping a minimum of every 5 ft. (1.5M)[3 ft. (.91M)
for SDR-21 or -26 PVC] using perforated metal hanging
strap or commercially available hangars designed to support
plastic pipe.
17. Prevent condensate from accumulating in the pipes by slop-
ing the combustion
air piping and vent piping downward
towards furnace a minimum of l/4-in, per linear ft. with no
sags between hangers.
18. Complete the vent and combustion air pipe installation by
connecting the concentric vent or by installing the required
termination elbows as shown in Fig. 47, 48 and 49.
For Ventilated Combustion Air Termination, See Fig. 50
19. Use appropriate methods to seal openings where combus-
tion air pipe and vent pipe pass through roof or sidewall.
Optional
Installation
of the vent pipe
This option provides a disconnect point for the vent pipe. The vent
pipe must be cemented to the plastic vent pipe adapter to maintain
a sealed vestibule. See Fig. 43.
1. Insert a length of vent pipe through the casing into the
outlet of the vent elbow.
43
ii

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents