Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions page 30

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

Unit Size
Table 7 - Cooling
4 and Heating
Air Delivery
- CFM
(Bottom
Return 5 with Filter)
(Continued)
Switch Settings
External Static Pressure (ESP)
SWx-1
CF Default:
OFF
See note 4
OFF
ON
745
705
680
See note 4
OFF
OFF
925
900
885
See note 4
OFF
ON
1100
1105
1085
See note 4
Cooling
(SW2)
....
ON
OFF
1255
1280
1275
1285
I 1270
1260
1250
1230
Cont Fan
(SW3)
....
ON
ON
1455
1465
1465
1470
I 1455
1450
1435
1415
ON
OFF
1855
1855
1850
1830
I 1805
1775
1750
1730
ON
ON
2200
2190
2185
2170
I 2145
2085
1990
1890
CIg SW2:
Maximum CIg Airflow 2
Heating
(SWl)
Low Heat Airflow 3
_. Set SW1-5 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW4-3 to ON for nominal 325 CFM/ton (-7% airflow).
Set both SW1-5 and SW4-3 to ON for nominal 370 CFM/ton (+7% airflow).
The above adjustments
in airflow
are subject to motor horsepower range/capacity.
2. Maximum cooling airflow is achieved when switches SW2-1, SW2-2, SW2-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
3. All heating CFM's are when low heat rise adjustment switch (SW1-3) and comfort/efficiency
adjustment switch (SW1-4) are both set to OFF.
4. Ductwork must be sized for high-heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not re-
commended because high-heat operation will be above 1.0 ESP.
5. All airflows on 21" (533 mm)casing size furnaces are 5% less on side return only installations.
6. Side returns for 24.5" (622 mm)casing sizes require two sides, or side and bottom, to allow sufficient airflow at the return of the furnace.
7. Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return; otherwise excessive watt draws may result. A
minimum filter size of 20" x 25" (508 x 635 mm) is required.
30