Carrier 110 Series Installation, Start-Up, Operating And Service And Maintenance Instructions

Single stage 4 -way multipoise condensing gas furnace

Advertisement

59SC5A
Single Stage 4---Way Multipoise
Condensing Gas Furnace
Series 110
Installation, Start---up, Operating and
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the
installation.
INTRODUCTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACCESSORIES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOCATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Upflow
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downflow
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Horizontal
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Upflow
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downflow
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Horizontal
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115- -V Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24- -V Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VENTING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Materials
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . .
. . . . . .
Adjustments
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
4
4
. . .
4
PARTS REPLACEMENT GUIDE
5
8
Loose Parts Bag
8
9
9
Filter Size Information
13
Opening Dimensions
13
Air Delivery CFM
13
13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
20
Combustion- -Air Vent Pipe, Fitting & Cement Material..
20
Maximum Allowable Exposed Vent Lengths Insulation
20
21
Deductions from Maximum Equivalent Vent Length
Blower Off Delay Setup Switch
21
29
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
29
31
32
32
33
33
33
33
37
Use of the AHRI Certified
.
37
manufacturer's participation in the program. For
verification of certification for individual products,
38
go to www.ahridirectory.org.
38
38
Portions of the text and tables are reprinted from NFPA 54/ANSI
39
Z223.1- -2012E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
41
Washington DC 20001. This reprinted material is not the complete
62
and official position of the NFPA or ANSI on the referenced
60
subject, which is represented only by the standard in its entirety.
60
1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
TABLES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
CERTIFIED
Mark indicates a
TM
60
60
. . . . . . . .
68
73
76
80
5
. . . . . . . . . . . . .
5
11
11
23
25
30
32
34
. . . . . . .
39
. . . . .
45
. . . . . .
46
47
. . . . . . . .
47
62
63
65
67

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 110 Series

  • Page 1: Table Of Contents

    59SC5A Single Stage 4---Way Multipoise Condensing Gas Furnace Series 110 Installation, Start---up, Operating and Service and Maintenance Instructions NOTE: Read the entire instruction manual before starting the Purge Gas Lines ........installation.
  • Page 2 Required Notice for Massachusetts Installations IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA- -54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:...
  • Page 3: Safety Considerations

    SAFETY CONSIDERATIONS CAUTION WARNING CUT HAZARD Failure to follow this caution may result in personal injury. FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and Failure to follow this warning could result in dangerous gloves when handling parts, and servicing furnaces.
  • Page 4: Codes And Standards

    13. These furnaces SHALL NOT be installed directly on carpet- B149.1- -2010 ing, combustible tile, or any other combustible material oth- General Installation er than wood flooring. In downflow installations, factory S US: NFGC and the NFPA 90B. For copies, contact the National accessory floor base MUST be used when installed on com- Fire Protection Association Inc., Batterymarch Park, Quincy, bustible materials and wood flooring.
  • Page 5: Minimum Clearances To Combustible Materials

    1. Disconnect all power to the furnace. Multiple disconnects surface of the furnace again before touching control or may be required. DO NOT TOUCH THE CONTROL wires. OR ANY WIRE CONNECTED TO THE CONTROL 5. Use this procedure for installed and uninstalled (ungroun- PRIOR DISCHARGING YOUR...
  • Page 6 A12267 59SC5 SHIP WT. LB (KG) FURNACE SIZE CABINET WIDTH OUTLET WIDTH BOTTOM INLET WIDTH AIR INTAKE 040--- 10 123.0 (55.4) 14--- 3/16 (361) 12--- 1/2 (319) 12--- 9/16 (322) 7--- 1/8 (181) 060--- 10 127.0 (57.2) 040--- 12 134.0 (60.9) 060--- 14 17--- 1/2 (445) 15--- 7/8 (403)
  • Page 7 THE BLOWER IS LOCATED BELOW THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED UPWARD. THE BLOWER IS LOCATED TO THE RIGHT OF THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED TO THE LEFT. THE BLOWER IS THE BLOWER IS LOCATED TO THE LEFT LOCATED ABOVE THE OF THE BURNER SECTION, BURNER SECTION, AND...
  • Page 8 LOCATION WARNING CAUTION CARBON MONOXIDE POISONING / COMPONENT DAMAGE HAZARD PERSONAL INJURY AND/OR PROPERTY Failure to follow this warning could result in personal injury DAMAGE HAZARD or death and unit component damage. Improper use or installation of this furnace may result in Corrosive or contaminated air may cause failure of parts premature furnace component failure.
  • Page 9: Air For Combustion And Ventilation

    CAUTION WARNING FIRE HAZARD FURNACE CORROSION HAZARD Failure to follow this warning could result in personal Failure to follow this caution may result in furnace damage. injury, death and/or property damage. Air for combustion must not be contaminated by halogen Do not install the furnace on its back or hang furnace with compounds, which include fluoride, chloride, bromide, and control compartment facing downward.
  • Page 10: Minimum Space Volumes

    The opening shall commence within 12 in. (300 mm) of the The following requirements apply to the Standard Method and to ceiling. Appliances in the space shall have clearances of at least 1 the Known Air Infiltration Rate Method. in. (25 mm) from the sides and back and 6 in. (150 mm) from the 1.
  • Page 11: Minimum Free Area Required

    Table 3 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors TWO OPENINGS OR TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING VERTICAL DUCTS (1 SQ. IN./2,000 BTUH) (1 SQ. IN./3,000 BTUH) (1 SQ. IN./4,000 BTUH) (1,100 SQ.
  • Page 12 * Minimum opening size is 100 sq in. (64516 sq. mm) with *Minimum dimensions of 3 in. (76mm) minimum dimensions of 3 in. (76mm) NOTE: Use any of the following combinations of openings: { Minimum of 3 in. (76mm) when type B1 vent is used. A &...
  • Page 13: Condensate Trap

    CONDENSATE TRAP NOTICE Condensate Trap - - Upflow Orientation When the furnace is installed in the upflow position, it is not The field- -supplied, accessory horizontal drain trap grommet is necessary to relocate the condensate trap or associated tubing. ONLY REQUIRED FOR DIRECT VENT APPLICATIONS. Refer to Fig.
  • Page 14 Remove pressure switch tube from front pressure switch and discard. A new tube is shipped in the loose parts bag. Remove relief tube from relief Remove tube from relief port. port on condensate trap. Remove the screw that secures the trap to the collector box and remove trap.
  • Page 15 Remove plug from If alternate vent position collector box. is required, loosen clamp DO NOT DISCARD. on inlet of vent elbow. Remove the screw that secures the trap to the collector box and remove trap. Unconverted Factory Configuration As Viewed in the Horizontal Right Orientation NOTE: Remove knockout in casing before re installing the condensate trap.
  • Page 16 Remove the screw that secures the condensate trap to the collector box If alternate vent position and remove trap. is required, loosen clamp on vent elbow inlet. Remove relief tube from relief port on condensate trap. Remove front pressure switch tube and discard. A new tube is shipped in the Loose Parts bag.
  • Page 17: Condensate Drain

    CONDENSATE DRAIN CONNECTION 4. From inside the casing, insert the formed grommet end of the elbow through the 7/8- -in. knockout in the casing. CAUTION 5. Pull the grommet through the casing from the outside until it is seated in the knockout 6.
  • Page 18 the other side of the casing should be facing the front of the 7. The remaining drain line can be constructed from field- - furnace. supplied 1/2- -in. CPVC or 3/4- -in. PVC pipe, in compliance with local building codes. A factory- -supplied 1/2- -in. 11.
  • Page 19 INSTALL CLAMPS ON DRAIN TUBE ATTACH DRAIN TUBE TO CONDENSATE DRAIN TRAP PULL DRAIN STUB THROUGH CASING NOTE: Trap grommet is required only for direct-vent applications. Remove knockout. Install grommet before relocating condensate OPEN SPRING CLAMP trap. INSERT FACTORY SUPPLIED 1/2 IN. CPVC TO 3/4 IN.
  • Page 20 INSTALLATION Leveling Legs (If Desired) In upflow position with side return inlet(s), leveling legs may be NOTICE used. See Fig. 22. Install field- -supplied, 5/16 x 1- -1/2 in. (8 x 38 mm) (max) corrosion- -resistant machine bolts, washers and nuts. NOTE: Bottom closure must be used when leveling legs are used.
  • Page 21: Filter Arrangement

    Return Air Connections Suspended Furnace Support The furnace must be supported under the entire length of the WARNING furnace with threaded rod and angle iron. See Fig. 29. Secure angle iron to bottom of furnace as shown. Roll- - Out Protection FIRE HAZARD Provide a minimum 12- -in.
  • Page 22 There are no provisions for an internal filter rack in these furnaces. An external filter is required and is purchased separately. A field supplied accessory air cleaner may also be used in place of the filter rack. For upflow applications, the filter can be installed on either side of the furnace, the bottom of the furnace or any combination of side and bottom of the furnace.
  • Page 23 Table 5 – Filter Media Pressure Drop (Clean) Versus Airflow - - In. W.C. (Pa) Representative After-Market Filter Media* 14 x 25 Filter Factory-Accessory Factory-Accessory (356 x 635 mm) Washable Media* Fiberglass* Pleated* (1-in. / 2.5 cm) (4-in. / 10 cm) (1-in.
  • Page 24 Table 7 – Air Filter Selection and Duct Sizing - - In. (mm) FILTER SIZE FURNACE CASING WIDTH FILTER TYPE SIDE BOTTOM RETURN RETURN 16 x 25 x 3/4 14 x 25 x 3/4 14 ---3/16{ (360) Washable* (406 x 635 x 19) (356 x 635 x 19) 16 x 25 x 3/4 16 x 25 x 3/4...
  • Page 25 FURNACE FURNACE (OR COIL CASING WHEN USED) APPROVED COIL ASSEMBLY COIL BOX COMBUSTIBLE COMBUSTIBLE FLOORING FLOORING PLENUM OPENING DOWNFLOW SUBBASE SHEET METAL PLENUM FLOOR SHEET METAL PLENUM OPENING FLOOR FLOOR OPENING OPENING A10491 Fig. 20 - - Installation on Combustible Flooring Table 8 –...
  • Page 26 UPFLOW DOWNFLOW HORIZONTAL PERFORATED DISCHARGE DUCT 90° 90° FLANGE 120° 120° 120° A10493 Fig. 21 - - Duct Flanges  5/ 16 (8mm) (8mm)  5/ 16  (44mm)  (44mm) (8mm)  BOTTOM CLOSURE PANEL (8mm) 5/ 16  3/ 4 ...
  • Page 27 ANY COMBINATION OF 1, 2, OR 3 PERMITTED. A11036 A11037 Fig. 25 - - Upflow Return Air Configurations and Restrictions Fig. 26 - - Downflow Return Air Configurations and Restrictions HORIZONTAL TOP RETURN NOT PERMITTED FOR ANY MODEL A11038 Fig. 27 - - Horizontal Return Air Configurations and Restrictions...
  • Page 28 COMBUSTION - AIR PIPE (SEE VENTING SECTION) 30 IN. (762 mm) MIN. WORK AREA 2-IN. (51 mm) ROLLOUT PROTECTION REQUIRED Install 12” x 22” (305 x 559 mm) sheet metal in front of burner compartment area. A11154 Fig. 28 - - Working Platform for Attic Installation NOTE: Local codes may require a drain pan and condensate trap when a condensing furnace is installed over a finished ceiling.
  • Page 29: Air Ducts

    AIR DUCTS NOTICE Many states, provinces and localities are considering or have implemented standards and/or restrictions on duct sizing practices, ductwork leakage, and/or ductwork thermal, airflow and electrical efficiencies. CONSULT LOCAL CODE OFFICIALS ductwork design performance requirements in your area. General Requirements The duct system should be designed and sized according to accepted national standards such as those published by: Air...
  • Page 30 Table 9 – Air Delivery - - CFM (With Filter) EXTERNAL STATIC PRESSURE (IN. W.C.) RETURN-AIR SPEED UNIT SIZE CONNECTION TAPS Black 1100 1055 1010 Yellow 040---10 SIDE/BOTTOM Blue Black 1245 1195 1150 1100 1050 1000 Yellow 1165 1120 1075 1030 040---12 SIDE/BOTTOM...
  • Page 31: Gas Piping

    GAS PIPING WARNING WARNING FIRE OR EXPLOSION HAZARD A failure to follow this warning could result in personal FIRE OR EXPLOSION HAZARD injury, death, and/or property damage. Failure to follow this warning could result in personal If local codes allow the use of a flexible gas appliance injury, death, and/or property damage.
  • Page 32: Electrical Connections

    Table 10 – Maximum Capacity of Pipe WARNING NOMINAL LENGTH OF PIPE --- FT (M) IRON PIPE SIZE ELECTRICAL SHOCK AND FIRE HAZARD (3.0) (6.0) (9.1) (12.1) (15.2) IN. (MM) 1/2 (13) Failure to follow this warning could result in personal injury, death, or property damage.
  • Page 33: J- -Box Installation

    J- -Box Installation 3. Secure power cord to J- -Box bracket with a strain relief bushing or a connector approved for the type of cord used. 4. Pull furnace power wires through 1/2- -in. (12 mm) diameter WARNING hole in J- -Box. If necessary, loosen power wires from strain—relief wire- -tie on furnace wiring harness.
  • Page 34: Electrical Data

    alternate power supply must produce a smooth sinusoidal Power from an alternate power supply that is non-sinusoidal may waveform for compatibility with the furnace electronics. The damage the furnace electronics or cause erratic operation. alternate power supply must generate the same voltage, phase, and Contact the alternate power supply manufacturer for specifications frequency (Hz) as shown in Table 11 or the furnace rating plate.
  • Page 35 To HUM Terminal On To Humidifier Leads Furnace Control Board 24 V Coil To Humidifier Leads To Com/24V Screw Terminal on Thermostat Strip A11157 Fig. 34 - - Field- -supplied Isolation Relay for Humidifiers with Internal Power Supply FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING...
  • Page 36 TWINNING AND/OR COMPONENT TEST BLOWER OFF-DELAY TERMINAL J2 JUMPER BLOWER OFF-DELAY HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) 24-V THERMOSTAT TERMINALS TRANSFORMER 24-VAC CONNECTIONS TEST/TWIN 0.5 AMP@24VAC 3-AMP FUSE FUSE 3-AMP SEC-2 SEC-1 LED OPERATION & EAC-2 DIAGNOSTIC LIGHT PL1-LOW VOLTAGE MAIN HARNESS CONNECTOR 115-VAC(L2)NEUTRAL CONNECTIONS...
  • Page 37: Special Venting Requirements For Installations In Canada

    VENTING NOTE: Planning for the venting system should be done in conjunction with planning for the ductwork, drainage, and furnace accessories, such as air cleaners and humidifiers. Begin assembling the venting system AFTER the furnace is set in place in the required orientation. Venting for this furnace shall follow all Local codes for Category IV venting systems.
  • Page 38: Venting Systems

    Other gas appliances with their own venting system may also use WARNING the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the National Fuel Gas Code, and the vent or liner manufacturer’s installation instructions. Care must CARBON MONOXIDE POISONING HAZARD be taken to prevent the exhaust gases from one appliance from Failure to follow the steps outlined below for each appliance...
  • Page 39: Locating The Vent Termination

    Table 12 – Vent Termination Kit for Direct Vent (2- -pipe) NOTICE Systems DIAMETER OF DIRECT VENT TERMINATION COMBUSTION AIR (2--- PIPE) OPTIONAL VENTING BELOW THE FURNACE SYSTEM AND VENT PIPES --- TERMINATION KIT IN. (mm) The venting system may be positioned below the furnace 2 ---in.
  • Page 40 Non-Direct Vent / 1-Pipe System NOTICE The vent pipe for a Non Direct Vent (1- -pipe) system must terminate outdoors. See Fig. 46 for references to vent clearances RECOMMENDED SUPPORT FOR required by National Code authorities. Allowable vent VENT TERMINATIONS terminations are shown in Fig.
  • Page 41: Combustion Air And Vent Piping Insulation Guidelines

    Length in Table 15 or 17, minus the number of fittings multiplied Venting Tables for elbows and flexible vent pipe. Factory by the deduction for each type of fitting used from Table 16. accessory concentric vent terminations or pipe lengths and elbows used for “standard”...
  • Page 42 The vent pipe may pass through unconditioned areas. The amount Installing the Vent Pipe Adapter and Combustion Air of exposed pipe allowed is shown in Table 14. Pipe Adapter 1. Using winter design temperature (used in load calculations), WARNING find appropriate temperature for your application and fur- nace model.
  • Page 43 3. Chamfer outside edge of pipe for better distribution of 1. Insert a length of vent pipe through the casing into the primer and cement. outlet of the vent elbow. 4. Clean and dry all surfaces to be joined. 2. Slide the plastic vent pipe adapter over the length of the vent pipe down to the furnace casing.
  • Page 44 NOTE: Do not allow insulation or other materials to accumulate guidelines provided in section “Locating The Vent Termination” in inside of pipe assembly when installing it through hole. this instruction. Disassemble loose pipe fittings. Clean and cement using same 1. Cut two holes, one for each pipe, of appropriate size for procedures as used for system piping.
  • Page 45 Table 13 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installations) ASTM SPECIFICATION SOLVENT CEMENT MATERIAL PIPE FITTINGS DESCRIPTION (MARKED ON MATERIAL) AND PRIMERS D1527 Pipe — — Schedule--- 40 D1785 Pipe — — Schedule--- 40 D2235 For ABS —...
  • Page 46 Table 14 – Maximum Allowable Exposed Vent Lengths Insulation Table - - Ft. / M Maximum Length of Uninsulated and Insulated Vent Pipe-Ft (M) No Insulation 3/8-in. (9.5 mm) Insulation 1/2-in. (12.7 mm) Insulation Single Winter Pipe Stage Design Pipe Diameter --- in. (mm) Pipe Diameter --- in.
  • Page 47 Table 15 – Maximum Equivalent Vent Length - - Ft. (M) 0 to 4500 Ft. (0 to 1370 M) Altitude NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Use Table 16 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application. DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE) Altitude Unit Size...
  • Page 48 Venting System Length Calculations The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of elbows used in the venting system from Table 16. Standard vent terminations or factory accessory concentric vent terminations count for zero deduction. See vent system manufacturer’s data for equivalent lengths of flexible vent pipe or other termination systems.
  • Page 49 Table 17 – Maximum Equivalent Vent Length - - Ft. (M) 4501 to 10,000 Ft. (0 to 1370 M) Altitude NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Use Table 16 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application. DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE) Altitude Unit Size...
  • Page 50 Attach gaskets to vent pipe and Vent Coupling and Adapter combustion air adapters. A13074 Fig. 37 - - Vent Coupling and Adapter with Gaskets INDUCER OUTLET VENT ELBOW CLAMP TORQUE 15 LB-IN. VENT PIPE CLAMP TORQUE 15 LB-IN. PSC INDUCER ASSEMBLY VENT ELBOW INDUCER OUTLET CHOKE 40,000 BTUH MODELS ONLY...
  • Page 51 Rotate vent elbow to required position. Any other unused knockout may be used for combustion air connection. Rotate vent elbow to required position. & UPFLOW LEFT CONFIGURATION DOWNFLOW LEFT CONFIGURATION A11309A A11311A Rotate vent elbow to required position. Any other unused Any other unused knockout may be used knockout may be used...
  • Page 52 ALTERNATE COMBUSTION AIR CONNECTIONS HORIZONTAL LEFT ---VERTICAL VENT CONFIGURATION HORIZONTAL RIGHT ---VERTICAL VENT CONFIGURATION A11327A A11337 Alternate combustion air connection. Rotate vent elbow to required position. Vent Pipe Requires Internal Vent Kit See Product Data for Current Kit Number HORIZONTAL RIGHT ---LEFT VENT CONFIGURATION HORIZONAL LEFT ---LEFT VENT CONFIGURATION A11328A A11336...
  • Page 53 NOTES FOR VENTING OPTIONS 1. Attach vent pipe adapter with gasket to furnace casing. 2. Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling. 3. Slide vent pipe through adapter and coupling into vent elbow. 4.
  • Page 54 A12326 NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations. (1 ) (2 ) Canadian Installations U.S. Installations Item Clearance Description (per CAN/CSA B149.1) (per ANSI Z223.1/NFPA 54) Clearance above grade, veranda, porch, deck, balcony...
  • Page 55 A12325 NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations. (1 ) (2 ) Canadian Installations U.S. Installations Item Clearance Description (per CAN/CSA B149.1) (per ANSI Z223.1/NFPA 54) Clearance above grade, veranda, porch, deck, balcony or...
  • Page 56 ¾ ¾ 12 in. (305mm) min. separation between bottom of combustion air and bottom of vent (Typ.) A13077 Fig. 47 - - Combustion Air and Vent Pipe Termination for Direct Vent (2- -Pipe) System Roof Termination (Preferred) Vent Maintain 12 in (305mm) minimum clearance above highest anticipated...
  • Page 57 OPTIONAL TERMINATION BRACKET FOR 2-PIPE TERMINATIONS OPTIONAL 12 IN. (305 MM) MIN. BRACKET SEPARATION BETWEEN COUPLING BOTTOM OFCOMBUSTION 12 IN. (305 MM) MIN. SEPARATION AIR AND BOTTOM OF VENT. BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT. MAINTAIN 12 IN. (305 MM) CLEARANCE ABOVE HIGHEST ANTICIPATED 12-IN.
  • Page 58 Ventilated Combustion Air intake pipe Pipe hangar 3” (76 mm) 12” (305 mm) Ventilated Combustion Air intake termination in crawl space CRAWL SPACE highest level of insulation ATTIC A10497 Fig. 50 - - Vent Terminations for Ventilated Combustion Air...
  • Page 59 EXAMPLE FOR UPFLOW INSTALLATIONS. MAY BE APPLIED TO OTHER CONFIGURATIONS. A12220 Fig. 51 - - Sample Inlet Air Pipe Connection for Polypropylene Venting Systems TO CODE APPROVED DRAIN OR CONDENSATE PUMP Representative drawing only, some models may vary in appearance L12F028 Fig.
  • Page 60: Start- -Up, Adjustment, And Safety Check

    START- -UP, ADJUSTMENT, AND SAFETY 1. Remove upper and middle collector box drain plugs oppos- ite of the condensate trap. See Fig. 59. CHECK 2. Connect field-supplied 5/8- -in. (16 mm) ID tube with at- General tached funnel to upper collector box drain connection. See Fig.
  • Page 61 (Furnace is shipped with No. 44 orifices. In this example, all main NOTICE burner orifices are the correct size and do not need to be changed to obtain proper input rate.) Manifold pressure: 3.4- -in. w.c. (847 Pa). The NATURAL GAS manifold pressure adjustments in Table 21 compensate for BOTH altitude AND gas heating value.
  • Page 62 (Read following caution before changing taps). WARNING CAUTION FIRE HAZARD Failure to follow this warning could result in personal UNIT DAMAGE HAZARD injury, death, and/or property damage. To avoid operating outside the rise range and avoid Reinstall manifold pressure tap plug in gas valve to prevent component damage: gas leak.
  • Page 63: Altitude Derate Multiplier For U.s.a

    Check Safety Controls Table 19 – Altitude Derate Multiplier for U.S.A. PERCENT DERATE ALTITUDE The flame sensor, gas valve, and pressure switch were all checked MULTIPLIER in the Start- -up procedure section as part of normal operation. DERATE FACTOR* 1. Check Main Limit Switch 0–2000 0--- 610 1.00...
  • Page 64 338309-201 Rev. E A11602 Fig. 56 - - Service Label Information...
  • Page 65: Gas Rate

    Table 20 – Gas Rate (CU ft./hr) SIZE OF TEST DIAL SIZE OF TEST DIAL SECONDS SECONDS FOR 1 REVOLUTION FOR 1 REVOLUTION 1 Cu Ft. 2 Cu Ft. 5 Cu Ft. 1 Cu Ft. 2 Cu Ft. 5 Cu Ft. 1800 1636 1500...
  • Page 66: Orifice Size And Manifold Pressure

    Table 21 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate SINGLE-STAGE FURNACE (TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL) ALTITUDE RANGE HEAT VALUE 0.58 0.60 0.62 0.64 AT ALTITUDE Orifice Manifold Orifice...
  • Page 67 Table 21 - - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Cont.) SINGLE-STAGE FURNACE (TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL) ALTITUDE RANGE HEAT VALUE 0.58 0.60 0.62 0.64 AT ALTITUDE Orifice...
  • Page 68: Service And Maintenance Procedures

    SERVICE AND MAINTENANCE The maximum break point of the switch is 0.73- -in. W.C. The maximum make point of the switch is 0.83- -in. W.C. PROCEDURES WARNING WARNING ELECTRICAL SHOCK HAZARD FIRE, INJURY OR DEATH HAZARD Failure to follow this warning could result in personal injury Failure to follow this warning could result in personal or death.
  • Page 69 Component Self-Test 6. Cycle test furnace with room thermostat to be sure that it operates properly with the room thermostat. Check all NOTE: The furnace control component test allows all modes including Heat, Cool and Fan. components to run for a short time; except the gas valve and 7.
  • Page 70 2. Check blower motor and wheel for cleanliness each heating The inducer and blower motors are pre- -lubricated and require no and cooling season. Clean as necessary. additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor. 3.
  • Page 71 13. Reinstall blower assembly in furnace. Refer to Fig. 14. Reinstall 2 screws securing blower assembly to blower 1. Disconnect power at external disconnect, fuse or circuit deck. breaker. 15. Reconnect blower leads to furnace control. Refer to furnace 2. Turn off gas at external shut-off or gas meter. wiring diagram, and connect thermostat leads if previously 3.
  • Page 72 13. Install the gas pipe to the gas valve. 1. Turn off gas and electrical supplies to furnace. 2. Remove control door. WARNING 3. Disconnect pressure switch tube from pressure switch port. NOTE: Ensure the pressure switch tube disconnected from the pressure switch is higher than the collector box opening or water FIRE OR EXPLOSION HAZARD will flow out of tube.
  • Page 73: Cleaning Heat Exchangers

    9. Turn gas on at electric switch on gas valve and at external 2. Remove control door. shut-off or meter 3. Disconnect wires or connectors to flame rollout switch, gas 10. Turn power on at external disconnect, fuse or circuit break- valve, igniter, and flame sensor.
  • Page 74 reach 32_F (0_C) or lower unless winterized. Follow these procedures to winterize your furnace: CAUTION 2 − in. (50 mm) UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the 3/8 − in. (9.6 mm) furnace and other property damage.
  • Page 75 GROMMET MOTOR SHAFT FLAT MOTOR ARM SCREW SET SCREW MOTOR WHEEL HUB SEE DETAIL SCREW LOCATION BLOWER HSG ASSY BRACKET BRACKET ENGAGEMENT DETAIL CUTOFF, BLOWER WHEEL, BLOWER BLOWER HSG ASSY BRACKET CAPACITOR OR POWER CHOKE (WHEN USED) MOTOR, BLOWER SCREW (GND) A11584 Fig.
  • Page 76: Sequence Of Operation

    SEQUENCE OF OPERATION Simultaneously, the electronic air cleaner terminal EAC- -1 is energized and remains energized as long as the blower NOTE: Furnace control must be grounded for proper operation or motor BLWM is energized. control will lock out. Control is grounded through green/yellow f.
  • Page 77 A11622 Fig. 64 - - Troubleshooting Guide...
  • Page 78 A12421 Troubleshooting Guide (Cont)
  • Page 79 A12420 Fig. 65 - - Wiring Diagram...
  • Page 80 The qualified installer or service agency must use only factory- -authorized replacement parts, kits, or accessories when modifying this product. Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 04/13 Catalog No: 59SC5A ---05SI Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.