Venting Systems; Locating The Vent Termination - Carrier 59TN6A Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier 59tn6a two-stage, variable speed multipoise gas furnace
Table of Contents

Advertisement

A furnace shall n otbeconnected
to a chinmey
flue serving
a
separate
appliance
designed
to burn solid fuel.
Other gas appliances
with their own venting
system
may also use
the abandoned
chinmey
as a raceway
providing
it is permitted
by
local code, the current
edition
of the National
Fuel Gas Code and
the vent or liner manufacturer's
installation
instructions.
Care must
be taken
to prevent
the exhaust
gases
from
one
appliance
from
contaminating
the combustion
air of other gas appliances.
Do not take combustion
air from
inside the chinmey
when
using
ventilated
combustion
air or single pipe vent option.
These
furnaces
can
be
vented
as either
direct
vent
furnace,
ventilated
combustion
air system
or non-direct
(single
pipe)
vent
system.
Each type of venting
system
is described
below.
Common
venting
between
furnaces
or other appliances
prohibited.
Materials
U.S.A.
Combustion
air and vent pipe, fittings,
primers,
and solvents
nmst
conform
to
American
National
Standards
Institute
(ANSI)
standards
and American
Society
for Testing and Materials
(ASTM)
standards.
See
Table
11 for approved
materials
for use
in the
U.S.A.
Canada
Special
Venting
Requirements
for
Installations
in
Canada
Installation
in
Canada
nmst
conform
to
the
requirements
of
CAN/CSA
B149
code. Vent systems
must
be composed
of pipe,
fittings,
cements,
and primers
listed to ULC $636.
Venting Systems
A factory
accessory
KGAVT
vent termination
kit nmst be used for
all direct vent terminations.
Termination
kits are available
for 2-in.
or 3-in. pipe. See Table
10 for available
options.
Table 10 - Vent Termination
Kit for Direct Vent (2-pipe)
Systems
DIRECT VENT
TERMINATION
DIAM. OF COMBUS-
(2-PIPE)
SYSTEM
TION AIR AND VENT
TERMINATION
KIT
PIPES - IN. (mm)
2-in.
(51 mm)
Single Penetration
of
1, 1-1/2,
2, or 2-1/2
Concentric
Vent Kit
Wall or Roof
(24, 36, 51,64 mm)
3-in.
(76 mm)
Single Penetration
of
2-1/2,
3 or 4
Concentric
Vent Kit
wall or Roof
(64, 76, 102 mm)
2-in.
(51 mm)
2-Pipe
Termination
1, 1-1/2
or 2
Termination
Bracket
Kit
System
(25, 36, 51 mm)
3-in.
(76 mm)
2-Pipe
Termination
2-1/2,
3 or 4
Termination
Bracket
Kit
System
(64, 76, 102 mm)
Direct
Vent
/ 2-Pipe System
In a direct-vent
(2-pipe)
system,
all air for combustion
is taken
directly
from
outdoor
atmosphere,
and
all
flue
products
are
discharged
to outdoor
atmosphere.
Combustion-air
and vent pipes
nmst
terminate
together
in the same
atmospheric
pressure
zone,
either through
the roof or a sidewall
(roof termination
preferred).
A
factory
accessory
vent termination
kit MUST
be used in a direct
vent (2-pipe)
system.
See Fig. 45 for required
clearances.
Ventilated
Combustion
Air
Systems
In a ventilated
combustion
air option,
the vent
terminates
and
discharges
the flue products
directly
to the outdoors
similar
to a
direct vent system.
See Fig. 46 for required
clearances.
All air for combustion
is piped
directly
to the furnace
from a space
that is well ventilated
with outdoor
air (such
as an attic or crawl
space)
and the
space
is well
isolated
from
the
living
space
or
garage.
Combustion
air requirements
for this option are the same as
the requirements
for providing
outside
air for combustion
for a
single
pipe vent system.
Refer
to the "Air For Combustion
and
Ventilation
Section.
Provisions
for adequate
combustion,
ventilation,
and dilution
air
must be provided
in accordance
with:
U.S.A.
Installations:
Section
9.3 NFPA
54/ANSI
Z223.1-2009,
Air for Combustion
and Ventilation
and applicable
provisions
of
the local building
codes.
Canadian
Installations:
Part 8 of CAN/CSA-BI49.1-10.
Venting
Systems
and Air Supply
for Appliances
and all authorities
having
jurisdiction.
Non-Direct Vent (1-pipe) System
In a non direct-vent
(1-pipe)
system,
all air for combustion
is taken
from
the
area
adjacent
to
furnace,
and
all flue
products
are
discharged
to outdoor
atmosphere.
Air
for combustion
nmst
be
supplied
as described
in the Air For Combustion
and Ventilation
Section.
Do not use an abandoned
chinmey
to supply outside
air to
the furnace.
See Fig. 46 for required
clearances.
Provisions
for adequate
combustion,
ventilation,
and dilution
air
must be provided
in accordance
with:
U.S.A.
Installations:
Section
9.3 NFPA 54/ANSI
Z223.1-2009,
Air
for Combustion
and Ventilation
and applicable
provisions
of the
local building
codes.
Canadian
Installations:
Part 8 of CAN/CSA-B149.1-10.
Venting
Systems
and Air Supply
for Appliances
and all authorities
having
jurisdiction.
A combustion
air pipe to the outdoors
is not required
for a single
pipe vent system.
A 12-in.
(304 ram) long
pipe with
a 2-in.
(51
ram) tight radius
90 degree elbow is required
to be attached
to the
combustion
air pipe adapter
on the furnace.
(See Fig. 44.)
Locating
the Vent Termination
General
NOTE:
Termination
Requirements
for
the
Provinces
of
Alberta
and
Saskatchewan
are
located
at the
end
of this
section.
Combustion-air
(direct
vent/2-pipe
system
only)
and vent
pipe
must terminate
outside
structure,
either through
sidewall
or roof.
For
vent
termination
clearance,
refer
to
Fig.
45
for
Direct
Vent/2-Pipe
system
and
Fig.
46
for
Non-direct
Vent/I-Pipe
system.
For exterior
termination
arrangements,
refer to Fig. 47 for
Direct
Vent/2-Pipe
system
and Fig.
48 for Non-
Direct/l-Pipe
system.
Roof termination
is preferred
since it is less susceptible
to damage
or contamination,
and
it has less
visible
vent
vapors.
Sidewall
terminations
require sealing or shielding
of building
surfaces
with a
corrosive
resistance
material
due to corrosive
combustion
products
of vent system.
NOTE:
(Direct
Vent/2-Pipe
system
ONLY)
A factory
accessory
termination
kit MUST
be used.
See Table
10 for available
options.
When
determining
appropriate
location
for termination,
consider
the following
guidelines:
1. Comply
with all clearance
requirements
stated in Fig. 45 or
Fig. 46 per application.
2. Termination
or termination
kit should
be positioned
where
vent
vapors
will not damage
plants/shrubs
or air condi-
tioning
equipment.
3. Termination
or termination
kit should
be positioned
so that
it will not be affected
by wind eddy, such as inside building
corners,
nor by recirculation
of flue gases,
airborne
leaves,
or light snow.
4. Termination
or termination
kit should be positioned
where it
will not be damaged
by or subjected
to foreign
objects
such
as stones,
balls, etc.
5. Termination
or termination
kit should
be positioned
where
vent vapors
are not objectionable.
Direct Vent / 2-Pipe System
Direct
vent (2-pipe)
vent and combustion
air pipes must terminate
outside
the structure.
Follow
all clearances
as shown
Fig.
45.
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents