6.3
Installing the boiler on a boiler base
or foundation
34 3/4"
34 3/4"
(~ 1160 mm)
4"
(100 mm)
16 9/64"
16 9/64"
(410 mm)
32 9/32"
32 9/32"
(820 mm)
Fig. 6
Base dimensions
A silencing boiler base is available as an
accessory from Buderus.
Place the boiler on a 2 – 4 inch (450 – 100 mm) tall base
(observe wall clearances). The base must be flat and level.
The front edge of the boiler should be flush with the edge
of the base.
When pouring a foundation for the boiler, use the steel
inserts with the following dimensions:
3 15/16 × 1 31/32 × 5/16 inches (100 × 50 × 8 mm)
or sheet metal with the dimensions
3 15/16 × 13/64 inches (100 × 5 mm).
Logano G615 - Subject to technical modifications
Number of
boiler sections
10
11
1
12
13
14
15
16
Tab. 9 Base dimensions for angle or sheet metal steel
6 720 642 621-01.1o
Positioning the boiler
L1 (base)
inch (mm)
9
65 3/4" (1670)
72 7/16" (1840)
79 9/64" (2010)
85 53/6"4 (2180)
92 33/64" (2350)
99 7/32" (2520)
105 29/32" (2690)
112 19/32" (2860)
lengths
6
L2 (steel section)
inch (mm)
57 7/8" (1470)
64 9/16" (1640)
71 1/4" (1810)
77 61/64" (1980)
84 41/64" (2150)
91 11/32" (2320)
98 1/32" (2490)
104 23/32" (2660)
17