Fitting Burner Door; Inserting The Flue Gas Baffles - Buderus Logano G615 Installation And Service Instructions Manual

Low-temperature oil/gas boiler boilers for oil/gas-fired power burners
Table of Contents

Advertisement

7.9.3

Fitting burner door

In the factory, the burner door is mounted with the hinges
on the right hand side. For left-hand closing, remove the
hinges from the right-hand side and reinstall them on the
left-hand side of the burner door.
B Place a few drops of Silastic adhesive, 6 – 8 inches
(15 – 20 cm) apart in the packing grooves on the front
section.
B Insert GP sealant rope into the packing groove on the
front section with the joint on the right or left hand side.
Position the sealant rope on the side.
B Screw the hinge pins (right-hand) to the boiler front
section with M12 × 55 machine screws in each case.
For left-hand closing, secure accordingly on the left-
hand side.
B Hook the burner door with the hinge lobes into the
hinge pins.
5
4
Fig. 30 Fitting burner door panel
1
Hinge pins (top)
2
Sealant rope (side)
3
Hinge pins (bottom)
4
Hinge lobe (bottom)
5
Holes in the burner door
6
Hinge lobe (top)
Logano G615 - Subject to technical modifications
6
3
2
6 720 642 625-27. o
Boiler block assembly
7.9.4

Inserting the flue gas baffles

In pre-assembled boilers, the flue gas baffles
are already fitted
B Remove the cardboard transport
protectors from the pre-assembled boiler.
The boiler consisting of 16 boiler sections
does not contain any flue gas baffles.
Flue gas baffles with sickle profile and wave
profile are being used in these boilers.
The flue gas baffles with sickle profile consist
of two pieces, and it is very important that
both parts are connected securely when
inserting the baffle into the boiler. When
fitting a hot gas flue with sickle profile baffles,
make absolutely certain that both partial
plates are hooked into one another.
Fig. 32, page 30 shows sectional and
interconnected baffles.
B Remove the flue gas baffles from the crate and insert
into the flue gas passages as indicated by their
inscription (
Fig. 31, Fig. 32, Fig. 33, and Tab. 11).
2
Fig. 31 Insert the flue gas baffles (boiler block with 9
sections)
1
Flue gas baffles with sickle profile (sectional baffle)
2
Flue gas baffles with sickle profile (interconnected)
7
6 720 642 625-28. o