9.2
Installing set of temperature
sensors
NOTICE: Appliance damage from damaged
capillaries.
B Make sure that the capillaries are not
crushed or otherwise compromised
during unrolling and routing.
B Route the capillaries through the cable duct and unroll
to the required length.
B Guide the capillaries to the corresponding sensor wells
and secure with the clips (magnified view in Fig. 53 is
rotated by 180°).
B Attach cable entry (
the boiler rear panel.
1
4
Fig. 53 Fastening the connecting cables
1
Sensor wells
2
Sensor retaining clip
3
Cable entry
4
Cable strain relief
Both sensor wells have already been installed in the
supply (
Chapter 7.5, page 24).
The sensors (control panel sensor TRK, manual reset high
limit and Logamatic sensor FK or thermostat sensor) are
installed in the sensor wells.
The manual reset high limit (STB) can be
distinguished from the control panel sensor.
The sensors must be arranged as follows:
Logano G615 - Subject to technical modifications
Fig. 52) to the left and right of
6 7 0 64 6 5-45.1o
B Push the control panel sensor TRK out of the sensor
spacer by pressing it lightly.
K
Fig. 54 Temperature sensor set
B Insert the control panel sensor in the sensor well R ½ "
and secure with a screw.
B Insert the manual reset high limit (STB) and Logamatic
FK plus the two sensor spacers in the sensor well
3
R ¾ " and secure with a clip.
Fig. 55 Installing set of temperature sensors
Installing the control panel
TRK
STB
K
R3/4"
TRK
R1/2"
9
STB
720 42 25-47.1o
720 42 25-48.1o
41