6
Positioning the boiler
6.2

Recommended wall clearances

50 7/16"
50 7/16"
(1281 mm)
≥ 15 3/4"
≥ 15 3/4"
(400 mm)
Fig. 5
Installation room with boiler
Observe the recommended wall clearances
for complete opening of the burner door, for
boiler installation and for cleaning and
maintenance (
The burner door can be hung with the hinges on the right
or left.
The wall clearance on the hinge side must be at least the
burner projection (AB). A distance of AB + 4"
(AB + 100 mm) from the wall is recommended.
16
AB + 4"
(AB+100 mm)
6 720 642 625-03.1o
Fig. 5 and Tab. 8).
Boiler capacity
BTU/h (kW)
Sections
1,944,921 –
9 – 12
2,797,956
(570 – 820)
3,139,170 –
13 – 16
4,094,570
(920 – 1200)
Tab. 8 Recommended and minimum wall clearances
If you do not observe the recommended minimum wall
clearances, you will not be able to use the cleaning kit.
Alternatively shorter cleaning devices or wet cleaning may
be used.
Logano G615 - Subject to technical modifications
Clearance A inch (mm)
Recommended
minimum
90 35/64"
55 1/8"
(2300)
(1400)
118 7/64"
59 1/16"
(3000)
(1500)