Recommended Wall Clearances - Buderus Logano G315 Installation And Service Instructions Manual

Low-temperature oil/gas boiler
Table of Contents

Advertisement

6
Positioning the boiler
6.2

Recommended wall clearances

34-41/64"
34 41/64"
(880 mm)
15-3/4"
≥ 15 3/4"
(400 mm)
Fig. 5
Installation room with boiler
Observe the recommended wall clearances for complete
opening of the burner door, for boiler installation and for
cleaning and maintenance Fig. 5.
The burner door can be hung with the hinges on the right
or left.
When installing your boiler maintain the recommended
minimum dimensions. Select the recommended
clearances between wall and boiler for easy access for
installation, maintenance and service work.
The wall clearance on the hinge side must be at least the
burner projection (AB). A distance of AB +4 inches
(AB + 100 mm) from the wall is recommended.
The length L
depends on the number of boiler sections
K
or boiler rating
Spare parts, page 51.
16
AB + 4"
(AB+100 mm)
6 720 642 621-02.1o
Boiler capacity
Boiler
MBH (kW)
sections
358 – 686
5 – 9
(105 – 230)
Tab. 8
If you do not observe the recommended minimum
clearance (
Fig. 5), you will not be able to use the
cleaning kit (accessory). Alternatively shorter cleaning
devices or wet cleaning may be used.
Logano G315 - Subject to technical modifications
Clearance A in inches (mm)
Recommended
Minimum
59 (1500)
39-3/8 (1000)