Input Specifications - Panasonic FP0 User Manual

Programmable controller
Hide thumbs Also See for FP0:
Table of Contents

Advertisement

Optional Memory
2.2
Specifications
2.2.3

Input Specifications

Item
Insulation method
Rated input voltage
Rated input current
Input impedance
Operating voltage range
Input points per
C10RM,
C10CRM,
common (*Note 1)
C10RS,
C10CRS
C14RM,
C14CRM,
C14RS,
C14CRS
C16T, C16CT,
C16P, C16CP
C32T, C32CT,
C32P, C32CP
T32CT,
T32CP
ON voltage/ON current
OFF voltage/OFF current
Response time
OFF ↔ ON
(at 24 V DC and 25
°C/66 °F)
ON ↔ OFF
Operating mode indicator
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) X0 through X5 are inputs for the high-speed counter and have
a fast response time. If used as normal inputs, we recommend
inserting a timer in the ladder program as chattering and noise
may be interpreted as an input signal.
2 − 14
Description
optical coupler
24 V DC
approx. 4.3 mA (at 24 V DC)
approx. 5.6 kΩ
21.6 to 26.4 V DC
6 points/common
8 points/common
8 points/common
16 points/common
19.2 V or less/3 mA or less
2.4 V or more/1 mA or more
50 µs or less (at X0, X1) (* Note 2)
100 µs or less (at X2 to X5) (* Note 2)
2 ms or less (at X6 to XF)
the same as above
LED
FP0