Panasonic FP0 User Manual page 276

Programmable controller
Hide thumbs Also See for FP0:
Table of Contents

Advertisement

Name
Boolean
Basic function instructions
On-delay
TML
timer
TMR
TMX
TMY
Auxiliary
F137
timer (16-bit)
(STMR)
Auxiliary
F183
timer (32-bit)
(DSTM)
Time
F182
constant
processing
Counter
CT
UP/DOWN
F118
counter
(UDC)
Note1) In the FP2/FP2SH/FP10SH, when timer 256 or higher, or counter 255 or lower, is used, the
number of steps is the number in parentheses. Also, in the FP2/FP2SH/FP10SH, when a timer
number or counter number has an index modifier, the number of steps is the number in
parentheses.
14-34
Symbol
After set value "n" x 0.001 seconds, timer contact "a" is set
to on.
After set value "n" x 0.01 seconds, timer contact "a" is set
to on.
After set value "n" x 0.1 seconds, timer contact "a" is set to
on.
After set value "n" x 1 second, timer contact "a" is set to on.
After set value "S" x 0.01 seconds, the specified output and
R900D are set to on.
After set value "S" x 0.01 seconds, the specified output and
R900D are set to on.
Executes the filter processing for the specified input.
Decrements from the preset value "n"
Increments or decrements from the preset value "S" based
on up/donw input.
Description
Steps
Note1)
3 (4)
3 (4)
3 (4)
4 (5)
5
7
9
3 (4)
5

Hide quick links: