Wiring The Rs232C Port - Panasonic FP0 User Manual

Programmable controller
Hide thumbs Also See for FP0:
Table of Contents

Advertisement

Wiring
7.9

Wiring the RS232C Port

7.9
Wiring the RS232C Port
When using the RS232C port, use the screw-down connection type terminal and the
wire according to the following procedures.
FP0 Control unit with RS232C port
(FP0 C10CRM/C10CRS/C14CRM/C14CRS/C16CT/C16CP/C32CT/C32CP)
RS232C port
terminal layout
Suitable wires (twisted wire)
− Size: AWG #28 to 16
− Conductor cross-sectional area: 0.08 to 1.25 mm
Use a shielded wire of the above wiring. We recommend grounding the shield section.
Also, if using a pole terminal, see * section 7.6.
7 − 20
SG: Signal Ground
RD: Receive Data
SD: Send Data
Item
Specification
Baud rate
300/600/1200/2400/4800/
9600/19200 bps
Transmission
3m/9.84 ft.
distance
Terminal block
Made by Phoenix Contact
Co. (3-pin)
Product number: MKDS
1/3-3.5
Communication
half-duplex
method
Settings when shipped from the factory
These are changed using system registers
412 to 414. The settings in effect when the
unit is shipped from the factory are noted
below.
412
RS232C port is not used.
413
Character bit: 8 bits
Parity check: odd
Stop bit: 1 bit
Header: without STX code
Terminator: CR
414
Baud rate: 9600 bps
2
FP0