Panasonic FP0 User Manual page 367

Programmable controller
Hide thumbs Also See for FP0:
Table of Contents

Advertisement

Error
Name
code
Compile
E6
memory
full error
High-level
E7
instruction
type error
High-level
instruction
E8
operand
combina-
tion error
No
E9
program
error
Rewrite
during
E10
RUN
syntax
error
Opera-
tion
Description and steps to take
status
The program is too large to compile in
the program memory.
⇒ Change to PROG. mode and reduce
the total number of steps for the
Stops
program.
-FP10SH
If memory expansion is
possible,compilation will become
possible when the memory is expanded.
In the program, high-level instructions,
which execute in every scan and at the
leading edge of the trigger, are
programmed to be triggered by one
contact. (e.g. F0 (MV) and P0 (PMV) are
Stops
programmed using the same trigger
continuously.)
⇒ Correct the program so that the high-
level instructions executed in every scan
and only at the leading edge are
triggered separately.
There is an incorrect operand in an
instruction which requires a specific
combination operands (for example, the
Stops
operands must all be of a certain type).
⇒ Enter the correct combination of
operands.
Program may be damaged.
Stops
⇒Try to send the program again.
When inputting with the programming
tool software,a delection,addition or
change of order of an
Conti-
instruction(ED,LBL,SUB,RET,INT,IRET,
nues
SSTP,and STPE) that cannot perform a
rewrite during RUN is being attempted.
Nothing is written to the CPU.
A A A A A
A A
A A A A
A A A A A A A A A
A A A A
A:Available
A A
A A
14-125