Analog I/O Unit
The I/O allocations of the analog I/O unit are determined by the position at which the unit
is installed.
Type
A21
Input: CH0 16 points
Input: CH1 16 points
Output: 16 points
A/D Converter Unit and Thermocouple Unit
The data of each channel switches and then reads or writes by the user program which
contains the conversion data switch flag.
Type
A80,
Input: CH0, 2, 4, 6
16 points
TC4,
TC4,
Input: CH1, 3, 5, 7
TC8
16 points
D/A Converter Unit
The data of each channel switches and then reads or writes by the user program which
contains the conversion data switch flag.
Type
A04V
Input: 16 points
A04I
A04I
Output: CH0, 2, 4, 6
16 points
Output: CH1, 3, 5, 7
16 points
I/O Link Unit
The I/O allocation of the I/O link unit is determined by order of connection.
Type
IOL
IOL
Input: 32 points
Input: 32 points
output: 32 points
output: 32 points
Note
Please verify with the manual for the FP0 CC−Link slave unit.
First expansion
Second
expansion
WX2
WX4
(X20 to X2F)
(X40 to X4F)
WX3
WX5
(X30 to X3F)
(X50 to X5F)
WY2
WY4
(Y20 to Y2F)
(Y40 to Y4F)
First expansion
Second
expansion
WX2
WX4
(X20 to X2F)
(X40 to X4F)
WX3
WX5
(X30 to X3F)
(X50 to X5F)
First expansion
Second
expansion
WX2
WX4
(X20 to X2F)
(X40 to X4F)
WY2
WY4
(Y20 to Y2F)
(Y40 to Y4F)
WY3
WY5
(Y30 to Y3F)
(Y50 to Y5F)
First expansion
Second
expansion
X20 to X3F
X20 to X3F
X40 to X5F
X40 to X5F
Y20 to Y3F
Y20 to Y3F
Y40 to Y5F
Y40 to Y5F
Specifications
12.2 I/O Allocation Table
Third expansion
WX6
(X60 to X6F)
WX7
(X70 to X7F)
WY6
(Y60 to Y6F)
Third expansion
WX6
(X60 to X6F)
WX7
(X70 to X7F)
Third expansion
WX6
(X60 to X6F)
WY6
(Y60 to Y6F)
WY7
(Y70 to Y7F)
Third expansion
X60 to X7F
X60 to X7F
Y60 to Y7F
Y60 to Y7F
12 − 9