Panasonic FP0 User Manual page 255

Programmable controller
Hide thumbs Also See for FP0:
Table of Contents

Advertisement

FP0
Add-
Item
ress
412
Selection of operation
413
Communication format
RS232C
port
setting
Baud
414
rate
setting
Unit no. (when
415
connecting C-NET)
416
Modem connection
Default
Name
Not used
(K0)
Start code:
None
Terminal
code: CR
Stop bit:
1 bit
Paritycheck:
With odd
Data length:
8 bits
(H3)
Setting by
9600
programming
(H1)
tool software
1
(K1)
Disable
(H0)
value
Using FPWIN GR
Not used
Computer link
General-purpose communication
Using FP programmer II
K0: RS232C port is not used.
K1: Computer link mode (when
connecting C-NET)
K2: Serial data communication mode
(general port)
Using FPWIN GR
- Data length: 7 bits/8bits
- Parity check: None/Odd/Even
- Stop bit: 1/2
* The following setting is valid only
when the communication mode
specified by system register 412 has
been set to "General-purpose serial
communication".
- Terminator CR/CR+LF/None/ETX
- Start code: STX not exist/STX exist
Using FP programmer II
Specify the setting contents using H
constants.
19200 bps
9600 bps
4800 bps
2400 bps
1200 bps
600 bps
300 bps
1 to 32 (K1 to K32)
Using FPWIN GR
Diable/Enable
Using FP programmer II
H0: Modem disabled
H8000: Modem enabled
Descriptions