List Of Electrical And Functional Parts; Outside Unit - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

List of Electrical and Functional Parts

3. List of Electrical and Functional Parts

3.1

Outside Unit

3.1.1 RWEYQ60, 72, 84MTJU
Item
Compressor
Inverter
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
High pressure
switch
Pressure
Low pressure sensor
protection
Fusible plug
Discharge gas temperature
protection
(Discharge pipe thermistor)
Temperature
protection
Inverter fin temperature
protection
(Radiator fin thermistor)
Others
Fuse
272
Name
Symbol
Type
M1C
OC protection
device
Y1E
Y2E
For M1C
HPS
S1NPL
R3T
R1T
F1U
For main PC
board
F2U
For cooling fan
F3U
motor
Model
RWEYQ60M, 72M, 84MTJU
JT100GCVDK@SA
26.5A
Fully closed: 0pls
Fully open: 2000pls
Fully closed: 0pls
Fully open: 2000pls
+0
OFF: 580
Psi
ON: 435±21.75Psi
−17.4
OFF: 10.15Psi
Open: 158~167°F
OFF: 275°F
OFF: 188.6°F
250V AC 10A Class B
250V AC 10A Class B
250V AC 5A Class B
SiUS30-604
Appendix

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents