Troubleshooting by Remote Controller Display / LED Display
5.8
"A6" Indoor Unit Fan Motor Lock
A6
Remote
Controller
Display
LED indications
The table below shows the LED indications.
Operation
Normal
Malfunctioning
Error generation
The error is generated when the fan rotations are not detected while the output voltage to the
fan is at its maximum.
Supposed
The possible causes are:
Causes
162
Malfunctioning indoor unit fan motor
Broken or disconnected wire
Malfunctioning contact
Malfunctioning indoor unit PC board.
HAP (green)
5
5
SiBE28-804
HBP (green)
5
5
Troubleshooting