Calibrating Analog Input (Analog Input)

6-6

Calibrating Analog Input (Analog Input)

6-6-1

Calibrating a Current Input

adj
30
a-20
c8e7
a--1
4677
In this example, calibration is shown for a Controller with an Analog Input, with
a current input set as the input type.
1,2,3... 1. Connect the power supply.
2. Connect an STV and DMM to the current input terminals, as shown in the
following diagram.
Input power supply
STV
DMM
Input power supply
STV
DMM
3. Turn the power ON.
4. Move to the calibration level.
This starts the 30-minute aging timer. This timer provides an approximate
timer for aging. After 30 minutes have elapsed, the No. 2 display changes
to 0. You can advance to the next step in this procedure even if 0 is not
displayed.
5. When the M Key is pressed, the status changes as shown to the left.
The No. 2 display at this time shows the currently entered count value in
hexadecimal. Set the STV to 20 mA.
Allow the count value on the No. 2 display to fully stabilize, then press the
D Key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
6. When the M Key is pressed, the status changes as shown to the left.
Set the STV to 1 mA.
Allow the count value on the No. 2 display to fully stabilize, then press the
D Key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
E5CN
9
Input power supply
10
4
STV
3
DMM
E5CN-U
10
Input power supply
11
2
STV
3
DMM
Section 6-6
E5AN/EN
1
2
19
18
E5GN
1
2
11
10
267