Placing The Boiler; Clearances - Buderus Logano G215 US Installation And Maintenance Instructions Manual

Oil and gas-fired boilers
Hide thumbs Also See for Logano G215 US:
Table of Contents

Advertisement

6

Placing the Boiler

6
Placing the Boiler
This chapter details how to install and place the boiler in
the boiler room.
SYSTEM DAMAGE
due to freezing temperatures.
Install the boiler in a frost-free room.
CAUTION!
6.1

Clearances

Position the boiler at the recommended clearances
(
Fig. 3). Reducing the minimum clearances makes
the boiler more difficult to access.
The boiler base or foundation must be perfectly flat and
level.
The burner door can be fitted with the hinge on the l.h.
or the r.h. side.
Mea-
sure
A
Recommended
minimum
B
Recommended
minimum
C
Recommended
minimum
L
see "Technical Data" chapter
K
Tab. 11 Recommended and minimum clearances
(in inches)
NOTICE
Reduced clearances must comply with
local and state codes. The boilers are
designed for a side clearance of 6". Make
sure that there is a sufficient clearance
between combustible materials and the
chimney connection as specified by
NFPA 31 (distance of 18").
NOTICE
Where applicable, allow extra wall
clearances for additional components,
for example hot water tank, pipe
connections, flue gas muffler or other
components on the flue gas side.
14
Installation and maintenance instructions Logano G215 US oil/gas-fired boilers • Issue 11/2004
Distance
51 1/8"
39 3/8"
27 1/2"
15 3/4"
15 3/4"
3 7/8"
Fig. 3
Boiler room clearances (see Tab. 11)
We reserve the right to make any changes due to technical modifications.