Before starting the TC12 software installation the Ethernet connection
should be configured using the instructions given in 2.2.2.5 or 2.2.2.6, as
appropriate.
(2)
Insert the TC12 Software disk into the PC and then switch the PC On. The
Installation software will auto-boot and 'SIEMENS' will be displayed for a
short time followed by the TC12 Instation PC Installation Screen, which
should look something like Figure 4 if the software is Version 7.4. If the
software is Version 8.3 it should something like Figure 5.
(3)
Check that the status for each IMD board is correctly indicated (see below
for possible display messages and actions).
If the Installation screen has locked up altogether and does not respond to
key presses check the Ram address switches are set up correctly on each
card (see section 2.2.2.8). If the switches are set correctly change to the
next available address as indicated in 2.2.2.8.1 and restart the installation.
(4)
Follow the instructions displayed for moving around the screen.
(5)
Select the type of Ethernet card that was installed in the PC from the
options on the 'Ethernet card' menu. (If an on-bard Ethernet connection is
being used, select the 'Panel PC (UM9008)' option.) On Version 7.4
software, move across to the 'Number of boards' menu and enter the
number of Ethernet cards that are installed in the PC - normally 1.
(6)
On version 8.3 Software, move to the 'Tune' menu and select YES or NO,
depending upon whether or not you wish the tune to be played when the
TC12 PC boots up. Move across to the 'SIP' menu and select YES if a SIP
is installed in the TC12 cabinet, otherwise select NO.
(7)
On Version 8.3 Software, move to the 'Comms' menu and select one of the
following options:
Modem
Direct/Flow Control
Direct/No Flow Cntrl
(8)
Check the status of the DIGI I/O cards shown in the Digital I/O box.
Correctly installed cards will show as 'OK', cards which are not installed will
show as 'Not installed' and cards which are incorrectly installed will show an
error message which may give a clue as to the nature of the problem.
(9)
Check the status of the IMD cards shown in the IMD Cards box. Correctly
installed cards will be shown as 'OK' together with 2 numbers separated by
a '/'. The first number is the address of the board and the second number
the IRQ number of the board. Also shown will be the type of IMD board
which has been detected, either 'Xi or Xe' or 'Xem'. Any boards which have
not been detected by the software will be shown as 'Not detected'.
666/HE/43100/000
TC12 Installation, Commissioning & Maintenance Handbook
If a conventional leased line is being used to connect
the Instation to the OTUs.
If direct Instation to outstation, RS232,
communications are being used with CTS/RTS
flow control.
If direct Instation to outstation, RS232,
communications are being used without
CTS/RTS flow control.