4.3.2.3 Connection to OTU PCB
There are two sockets on the front of the OTU PCB. The sockets are labelled on
the silk screen. The top socket is reply and the bottom socket is control.

4.3.3 Front Panel Switches

4.3.3.1 Mains Switch
Mains switch and PC switch
Switching the Test Set off, using the rocker switch on the front panel, does NOT
guarantee isolation from the mains.
4.3.3.2 Modem Mode Switch and Mode Set Switch
To select the transmission mode the following procedure should be followed;
Press and hold down the modem set button (before moving the modem mode
select switch).
Whilst keeping the mode set button depressed, turn the modem mode switch to
the appropriate setting.
Release the modem set button.
Note. If the modem set button is not depressed whilst the modem mode select
switch is being moved, the test set may enter an unknown mode.
BELL Modes:
Switch Setting (Baud)
1200 equ
1200
300
CCITT Modes:
Switch Setting (Baud)
1200 equ
1200
600
300
Note Selections at 300 Baud are Originate when the test set is in Instation
mode and Answer when the test set is in Outstation mode, and a mixture
when in monitor mode (i.e. test set modem 1 control in Answer mode, test
set modem 2 reply in Originate mode). This requirement is an automatic
selection made by the test logic board. The user simply has to select 300
baud and ITS mode.
666/HE/43100/000
TC12 Installation, Commissioning & Maintenance Handbook
Full Description
Bell 202 with Equaliser Loopback
Bell 202 Main Loopback
Bell 103
Full Description
CCITT V.23 M2 with Equaliser Loopback
CCITT V.23 M2 Main Loopback
CCITT V.23 M1
CCITT V.21
Page 142
Issue 10