KAD 3 = 2
KAD 4 = 3
Select normal lamp monitoring (not RLM) on vehicle phases:
Note: Sensors 3 and 4 do not monitor vehicle phases and so their configuration
does not need to be changed.
KRE 1 = 0
KRE 2 = 0
Example 4 - Pelican (single current sensor)
Description:
In this example, the pelican is monitored with a single current sensor (see example
5 for separate wait and pedestrian and vehicle monitoring using three current
sensors)
The configuration commands are detailed below.
Enable LMU write access:
AMB = 35
NEC = 249
Allocate function of current sensor 1:
KPT 1 = 11
Allocate the mains state inputs associated with each current sensor:
Note: Input numbers 1 to 32 on the buffered input connector are referenced as 0
to 31 on the handset commands.
KMS 0 1 = 31
KMS 1 1 = 30
KMS 2 1 = 29
Allocate aspect drive identity to each current sensor:
KAD 1 = 0
Example 5 - Pelican (three current sensors)
Description:
666/HE/43100/000
TC12 Installation, Commissioning & Maintenance Handbook
:sensor 3 is phase C
:sensor 4 is phase D
:sensor 1
:sensor 2
This is a pelican controller with dimming.
:the current sensor monitors a complete
:pelican stream
:sensor 1 vehicle green is on digital input 32
:sensor 1 pedestrian green is on digital input 31
:sensor 1 wait is on digital input 30
:sensor 1, vehicle is phase A (and so
by implication, the pedestrian is phase B)
This is a pelican controller with dimming.