junction have been learnt in that state. If the learning of the second state is left to
occur automatically at the next dim/bright change, and the lamp failure occurs
during or just after the change, it will not be detected by the LMU until the
controller reverts back to the original state in which the junction learning was
invoked.
3.3.4.4 Checking that Lamp Failures are Detected
The installation engineer may check that lamp failures are indicated when they
occur and that lamp replacements remove the fault indication.
These checks should be carried out after the junction characteristics have been
learnt.
Remove any lamp and wait for the LMU to find the failure. Indication that the lamp
failure has been found will be given by the lighting of the system fail LED on the
OTU PCB, and by the appropriate entry in the fault log. The installation engineer
may check that fault information produced by the LMU is recognised by the
equipment (OTU or controller) to which the fault outputs are connected if required.
Further lamps may be removed to check that lamp failures can be detected on
other controller outputs.
666/HE/43100/000