Switching the motor on and off in the jog mode
Figure 5-3
In the case of converters with a PROFIBUS or PROFINET interface, operation can be switched
via digital input DI 3. The motor is either switched on and off via the fieldbus – or operated in
the jog mode via its digital inputs.
When a control command is received at the respective digital input, the motor rotates at
±150 rpm. The same ramp-up and ramp-down times as described above apply.
5.3.3

Minimum and maximum speed

Minimum and maximum speed
• Minimum speed - factory setting 0 [rpm]
The minimum speed is the lowest speed of the motor independent of the speed setpoint. A
minimum speed > 0 is, for example, useful for fans or pumps.
• Maximum speed - factory setting 1500 [rpm]
The converter limits the motor speed to the maximum speed.
Operate the converter with the factory setting
We recommend that you execute quick commissioning. For quick commissioning, you must
adapt the converter to the connected motor by setting the motor data in the converter.
In basic applications with a standard induction motor, you can attempt to operate the drive
with a rated power of < 18.5 kW without carry out an additional commissioning steps.
Check whether the control quality of the drive without commissioning is adequate for the
requirements of the application.
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Jogging the motor with the factory settings
Commissioning
5.3 Preparing for commissioning
123