Advanced commissioning
8.19 PID technology controller
Number
p2350
p2354
p2355
298
Name
Enable PID autotuning
Automatic controller setting based on the "Ziegler Nichols"
method.
After completion of the autotuning, the converter sets
p2350 = 0.
0: No function
1: The process variable follows the setpoint after a sudden
setpoint change (step function) relatively quickly, however
with an overshoot.
2: Faster controller setting than for p2350 = 1 with larger
overshoot of the controlled variable.
3: Slower controller setting than for p2350 = 1. Overshoot of
the controlled variable is, to a large extent, avoided.
4: Controller setting after completion of the autotuning as for
p2350 = 1. Optimize only the P and I action of the PID con‐
troller.
 
PID autotuning monitoring time
PID autotuning offset
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Factory setting
0
240 s
5%
SINAMICS G120C Converters