Advertisement

Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Application class
Max. output fre‐
quency
Commissioning
5.4.4

Standard Drive Control

Function description
Select the motor standard:
Set the converter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
Motors with motor code stamped on the rating plate:
Depending on the converter, the motor list in BOP‑2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
converter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor
data from p0304 and higher from the rating plate.
87 Hz motor operation The BOP‑2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = kW 50 Hz).
128
Standard Drive Control
550 Hz
Unlike "Dynamic Drive Control," no speed con‐
troller needs to be set
When compared to "Expert":
– Simplified commissioning using prede‐
fined motor data
– Reduced number of parameters
"Standard Drive Control" is preset for convert‐
ers frame size A ... frame size C
: IEC
: NEMA, US units
: NEMA, SI units
: Third-party induction motor
: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
: 1LE1 . 9
: 1PC1
: Induction motor
Dynamic Drive Control
Fewer number of parameters when compared to
setting "Expert"
"Dynamic Drive Control" is preset for converters
frame size D ... frame size F
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK