Installing
4.12 Monitoring the temperature of the braking resistor
Procedure
1. Connect the temperature monitoring system of the braking resistor (terminals T1 and T2 on
the braking resistor) to a free digital input on the converter.
Figure 4-48
2. Define the function of the digital input used as an external fault with p2106.
As an example with temperature monitoring via digital input DI 3: p2106 = 722.3.
You have ensured that the temperature is monitored.
118
Example: Temperature monitoring of the braking resistor via digital input DI 3 on the
Control Unit
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK