Electric shock due to unconnected cable shield
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
• As a minimum, connect cable shields and the conductors of power cables that are not used
Arcing when a plug connection is opened during operation
Opening a plug connection when a system is in operation can result in arcing that may cause
serious injury or death.
• Only open plug connections when the equipment is in a voltage-free state, unless it has
Electric shock due to residual charges in power components
Because of the capacitors, a hazardous voltage is present for up to 5 minutes after the power
supply has been switched off. Contact with live parts can result in death or serious injury.
• Wait for 5 minutes before you check that the unit really is in a no-voltage condition and start
NOTICE
Damage to equipment due to unsuitable tightening tools.
Unsuitable tightening tools or fastening methods can damage the screws of the equipment.
• Only use screw inserts that exactly match the screw head.
• Tighten the screws with the torque specified in the technical documentation.
• Use a torque wrench or a mechanical precision nut runner with a dynamic torque sensor and
• Adjust the tools used regularly.
NOTICE
Property damage due to loose power connections
Insufficient tightening torques or vibration can result in loose power connections. This can
result in damage due to fire, device defects or malfunctions.
• Tighten all power connections to the prescribed torque.
• Check all power connections at regular intervals, particularly after equipment has been
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
WARNING
(e.g. brake cores) at one end at the grounded housing potential.
WARNING
been explicitly stated that they can be opened in operation.
WARNING
work.
speed limitation system.
transported.
Fundamental safety instructions
1.1 General safety instructions
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c uss/mbSinamics g120c dpSinamics g120c pn

Table of Contents