Advanced commissioning
8.4 Adapt the default setting of the terminal strip
8.4.4

Digital outputs

Function description
To change the function of a digital output, you must interconnect the digital output with a
binector output of your choice.
Binector outputs are designated in the parameter list with "BO".
Example
To output converter fault messages via digital output DO 1, you must interconnect DO 1 with
these fault messages.
Set p0731 = 52.3
Parameter
Table 8-3
Parameter
r0052[0...15] CO/BO: Status word 1
192
Frequently used binector outputs (BO) of the converter
Description
.00
1 signal: Ready for switching on
.01
1 signal: Ready for operation
.02
1 signal: Operation enabled
.03
1 signal: Fault active
.04
0 signal: OFF2 active
.05
0 signal: OFF3 active
.06
1 signal: Switching on inhibited active
.07
1 signal: Alarm active
.08
0 signal: Deviation, setpoint/actual speed
.09
1 signal: Control request
.10
1 signal: Maximum speed (p1082) reached
.11
0 signal: I, M, P limit reached
.13
0 signal: Alarm, motor overtemperature
.14
1 signal: Motor clockwise rotation
.15
0 signal: Alarm, converter overload
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK