Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Figure 5-9
Figure 5-10
Ramp-down time for the OFF3 command
Motor data identification: Select the method which the converter uses to measure the data of
the connected motor:
•
•
motor rotating. The converter switches off the motor after the motor data identification has
been completed.
•
motor data identification has been completed.
Select this setting if one of the following cases is applicable:
– You have selected control mode
– You have selected U/f control as control mode, e.g.
•
motor after the motor data identification has been completed.
•
After the motor data identification, the motor accelerates to the current setpoint.
•
After the motor data identification, the motor accelerates to the current setpoint.
Complete the data entry for quick commissioning as follows:
1. Switch over the display using an arrow key:
2. Press the OK key.
You have entered all of the data that is necessary for the quick commissioning of the
converter.
❒
136
Minimum and maximum motor speed
Ramp-up and ramp-down time of the motor
: Motor data is not measured.
: Recommended setting: Measure the motor data at standstill and with the
: Measure the motor data at standstill. The converter switches off the motor after the
: Measure the motor data while the motor is rotating. The converter switches off the
: Setting the same as
: Setting the same as
; however, the motor cannot rotate freely.
→