System Design and Installation
Correct: Properly twisted
• Separate power supply cables and signal cables when wiring.
Selecting Components
This section explains the criteria for selecting the connection components required for
improving noise resistance. These criteria include capacity performance, applicable
range, and so on. For more details, contact the manufacturers directly.
No-fuse Breakers (NFB)
When selecting no-fuse breakers, take into consideration the maximum output current and the inrush
current.
Maximum input current:
The momentary maximum output for a Servo Driver is approximately three times that of the rated
output, and a maximum output of three seconds can be executed. Therefore, select no-fuse breakers
with an operating time of at least five seconds at 300% of the rated maximum output. General-pur-
pose and low-speed no-fuse breakers are generally suitable. The table in 3-2-3 Terminal Block Wir-
ing shows the rated power supply input currents for each Servomotor. Select a no-fuse-breaker with
a rated current greater than the total effective load current (when multiple Servomotors are used).
When making the selection, add in the current consumption of other controllers, and so on.
Servo Driver inrush current:
With low-speed no-fuse breakers, an inrush current 10 times the rated current flows for 0.02 sec-
onds. For a simultaneous inrush for multiple Servo Drivers, select a no-fuse-breaker with a 20-ms
allowable current greater than the total inrush current shown in the following table for the applicable
Servomotor models.
Smart
Power
Servo
supply
Driver
voltage
V
Single-
100
phase
100
100
100
100
Driver
L1C
L2C
Servo
Capacity
Driver
model
(R7D-)
APA3L
30 W
APA5L
50 W
AP01L
100 W
AP02L
200 W
AP04L
400 W
Correct: Cables are bound.
or
Binding
Rated
Inrush
current
current
circuit
A (rms)
A (0-p)
1.64
90
2.2
90
4
90
6.8
90
11
90
Chapter 3
Driver
L1
L2
L3
125% of
NFB model
rated
current
2.05
NF30-SW 10A
2.75
NF30-SW 10A
5
NF30-SW 10A
8.5
NF30-SW 10A
13.75
NF30-SW 15A
3-21