6-Phase/12-Pulse 400 V Class - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Rated Output Current
Model
4009
4012
4018
4023
4031
4038
4044
4060
4075
4089
4103
4140
4168
4208
4250
4302
4371
4414
4477
4568
4605
4720

6-Phase/12-Pulse 400 V Class

Rated Output Current
Model
T103
T140
T168
T208
T250
T302
T371
T414
T477
T568
T605
T720
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Carrier Frequency
A
kHz
8.9
2
11.9
2
17.5
2
23.4
2
31
2
38
2
44
2
59.6
2
74.9
2
89.2
2
103
2
140
2
168
2
208
2
250
2
296
2
371
2
389
2
453
2
568
2
675
2
720
2
Table 2.5 Drive Watt Loss (Heavy Duty)
Carrier Frequency
A
kHz
91
8
112
5
150
5
180
5
216
5
260
5
304
5
371
5
414
2
453
2
605
2
605
2
Interior Unit Loss
Cooling Fin Loss
W
W
42
58
57
84
82
144
108
185
138
222
145
270
168
335
157
444
185
527
212
665
264
766
393
1126
574
1348
493
1465
686
1738
817
2257
1022
2553
873
2422
1183
3329
1429
3989
1526
4572
1723
5184
Interior Unit Loss
Cooling Fin Loss
W
W
208
750
256
912
352
1139
400
1385
490
1397
616
1985
638
2499
625
2212
911
2835
1042
3329
1184
4110
1203
4198
2.5 Drive Watt Loss
Total Loss
W
100
141
226
293
360
415
503
601
712
877
1030
1519
1922
1958
2424
3074
3575
3295
4512
5418
6098
6907
2
Total Loss
W
958
1168
1491
1785
1887
2601
3137
2837
3746
4371
5294
5401
43

Advertisement

Table of Contents
loading