Drive Watt Loss; Class - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

2.5

Drive Watt Loss

200 V Class
Rated Output Current
Model
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
2169
2211
2257
2313
2360
2415
Rated Output Current
Model
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
2169
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Table 2.1 Drive Watt Loss (Heavy Duty)
Carrier Frequency
A
kHz
3.5
8
5
8
6.9
8
8
8
11
8
14
8
17.5
8
25
8
33
8
47
8
60
8
75
8
88
8
115
8
145
5
180
5
215
5
283
5
346
5
415
5
Table 2.2 Drive Watt Loss (Normal Duty)
Carrier Frequency
A
kHz
4.2
2
6
2
8
2
9.6
2
12.2
2
17.5
2
21
2
30
2
42
2
56
2
70
2
82
2
110
2
138
2
169
2
Interior Unit Loss
Cooling Fin Loss
W
W
35
19
37
26
40
36
44
43
50
61
47
82
56
105
74
174
88
183
112
267
145
373
179
478
155
563
212
680
275
820
314
991
398
1252
502
1643
582
1978
644
2359
Interior Unit Loss
Cooling Fin Loss
W
W
35
18
38
25
42
34
49
46
56
62
53
88
75
125
95
206
129
227
149
302
177
403
202
467
192
631
269
814
338
941
2.5 Drive Watt Loss
Total Loss
W
54
63
76
87
111
129
161
248
271
379
518
657
718
892
1095
1305
1650
2145
2560
3003
2
Total Loss
W
53
63
76
95
118
141
200
301
356
451
580
669
823
1083
1279
41

Advertisement

Table of Contents
loading

Table of Contents